2.3.2

Amount of heat generated by the inverter

Installing the heat sink inside the enclosure
When the heat sink is installed inside the enclosure, the amount of heat generated by the inverter unit and the converter unit is
shown in the following tables.
Converter
FR-CC2-H[]
355K
2600
400K
3050
450K
3400
500K
3800
560K
4400
630K
4920
Inverter
FR-F842-[]
07700(355K)
5800
08660(400K)
6690
09620(450K)
7370
10940(500K)
8600
12120(560K)
9810
NOTE
• The amount of heat generated shown assumes that the output current is the inverter rated current, and the carrier frequency
is 2 kHz.
Protruding the heat sink through a panel
When the heat sink is protruded through a panel, the amount of heat generated by the inverter unit and converter unit is
shown
in the following tables. (For the details on protruding the heat sink through a panel, refer to
Converter
FR-CC2-H[]
355K
1820
400K
2130
450K
2380
500K
2660
560K
3080
630K
3440
Converter
FR-F842-[]
07700(355K)
4060
08660(400K)
4680
09620(450K)
5160
10940(500K)
6020
12120(560K)
6860
NOTE
• The amount of heat generated shown assumes that the output current is the inverter rated current, and the carrier frequency
is 2 kHz.
Amount of heat generated (W)
Amount of heat generated (W)
SLD
LD
5050
5800
6480
7340
8630
Heat sink section (outside of enclosure)
Heat sink section (outside of enclosure)
SLD
3530
4060
4530
5140
6040
Installation of the inverter and enclosure design
Amount of heat generated (W)
Control section (inside of enclosure)
780
920
1020
1140
1320
1480
Amount of heat generated (W)
Control section (inside of enclosure)
LD
SLD
1740
2010
2210
2580
2950
INSTALLATION AND WIRING
page
23.)
LD
1520
1740
1950
2200
2590
2
19

Advertisement

Table of Contents
loading