PLACEMENT CONSIDERATIONS

Outdoor Unit Clearance Requirements

Outdoor Unit Installation Space
Proper airflow through the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet, and
outlet, and minimum allowable space requirements as illustrated in the diagrams below.
Description
Unit(s) is (are)
Enclosed by
Four (4) Walls
Unit(s) is (are)
Facing Away
From Each
Other
(To the Rear)
Two (2) Sides
Are Enclosed
By Walls
Different clearances are required if a Low Ambient Cooling Kit is installed. Refer to the Low Ambient Cooling Kit Installation Manual for clearance
information.
32
Installation Area
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
No Limitations on Wall Height
Front
No Limitations on Wall Height
Front
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Example No. 1
Example No. 2
A ≥ 1"; C ≥ 2"
A ≥ 2"; C ≥ 2"
A ≥ 1"
A ≥ 2"
B ≥ 12"
B ≥ 4"
C ≥ 1"
C ≥ 2"
D ≥ 20"
D ≥ 20"
A ≥ 1"
A ≥ 2"
B ≥ 12"
B ≥ 4"
C ≥ 1"
C ≥ 2"
D ≥ 20"
D ≥ 20"
E ≥ 1"
E ≥ 4"
A ≥ 1"
A ≥ 2"
B ≥ 20"
B ≥ 4"
C ≥ 1"
C ≥ 2"
D ≥ 20"
D ≥ 20"
E ≥ 1"
E ≥ 4"
F ≥ 36"
F ≥ 20"
A ≥ 1"
A ≥ 2"
B ≥ 12"
B ≥ 4"
C ≥ 1"
C ≥ 2"
D ≥ 12"
D ≥ 4"
E ≥ 1"
E ≥ 4"
F ≥ 20"
F ≥ 20"
A ≥ 1"
A ≥ 2"
B ≥ 20"
B ≥ 20"
C ≥ 1"
C ≥ 2"
D ≥ 20"
D ≥ 20"
F ≥ 36"
F ≥ 24"
A ≥ 1"
A ≥ 2"
B ≥ 20"
B ≥ 20"
C ≥ 1"
C ≥ 2"
D ≥ 20"
D ≥ 20"
E ≥ 1"
E ≥ 4"
F ≥ 48"
F ≥ 36"
A ≥ 1"
A ≥ 2"
B ≥ 20"
B ≥ 20"
C ≥ 1"
C ≥ 2"
D ≥ 20"
D ≥ 20"
E ≥ 1"
E ≥ 4"
F ≥ 71"
F ≥ 48"
A ≥ 1"
B ≥ 12"
A ≥ 8"
B ≥ 12"
E ≥ 16"