LG ARUM072BTE5 Installation Manual page 91

Multi v 5 series
Hide thumbs Also See for ARUM072BTE5:
Table of Contents

Advertisement

2. Inverted traps are required when:
a. Piping in a horizontal direction from the outdoor Y-branch towards an outdoor unit or another outdoor unit Y-branch is greater than 6.6'.
The inverted trap should be installed close to the outdoor unit Y-branch (no more than 6.6' away).
b. Anytime piping turns downward leaving an outdoor unit Y-branch toward an outdoor unit or another outdoor unit Y-branch.
The inverted trap should be installed close to the outdoor unit Y-branch (no more than 6.6' away), and before the pipe toward the outdoor
unit turns downward.
Examples of Inverted Traps.
To IDUs / HRUs
Oil Trap
Pipe Slope
Horizontal pipe slope should be level or slightly away from the
outdoor units, otherwise refrigerant and oil will migrate toward the
outdoor units and accumulate in the pipe segment serving the frame
that is not running or at the lowest elevation. Piping should never
slope more than -10° (see figure) without installing an inverted trap
within 6.6' of the outdoor unit Y-branch and before the pipe slopes
downward toward the outdoor unit.
Inverted Trap Applications.
To IDUs /
HRUs
Oil Trap
To IDUs / HRUs
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
REFRIGERANT PIPING FOR
SEPARATED OUTDOOR UNITS
Oil Trap
Oil Trap
Oil Trap
Oil Trap
Allowable Pipe Slope.
To indoor units /
heat recovery units
Oil Trap
-10°
91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents