PRE-COMMISSIONING
Addressing with Heat Recovery Units
2. SW05M Function (Rotary Switch for Addressing Heat Recovery Units).
• Rotary switch SW05M must be
set to "0"' when installing only
one heat recovery unit.
• When installing multiple heat
recovery units, address each
unit with sequentially increas-
ing numbers starting from "0".
3. SW01M / SW03M / SW04M (DIP and Tact Switches) for Manual Valve
Addressing
Non-zoning (Normal Setting).
• Set the address of the heat recovery unit valve to the central control address of the connected indoor unit.
• SW01M: Select the valve to address.
• SW03M: Increases the valve address by ten (10).
• SW04M: Increases the valve address by one (1).
Each indoor unit must have a unique, preset central control address (using its wired controller) before manual valve addressing can occur.
Table 69: Settings for Manual Valve Addressing, Non-Zoning.
PCB Component
SW01M
ON
OFF
3 4
5
6 7 8
1
3
4
5
6
7 8
1 2
SW01M
ON
OFF
3 4
5
6 7 8
1
1 2
3
4
5
6
7 8
146
Adjusting the Heat Recovery Unit Addresses.
S/W No.
No. 1
No. 2
No. 3
2 3 4
No. 4
3
4
Turn the DIP Switch of the zoned
SW03M
branch to ON.
Example: Branches one (1) and
2 3 4
two (2) are set to zone control.
3
4
SW04M
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
A B
3 4
1 2
Increases the Valve Address by Ten (10)
Increases the Valve Address by One (1)
A B
3 4
1 2
Set Up
Manual Addressing Valve No. 1
Manual Addressing Valve No. 2
Manual Addressing Valve No. 3
Manual Addressing Valve No. 4
A B
3 4
1 2