Outdoor Unit Location Selection - LG LGRED LH188HHV1 Installation Manual

Single-zone convertible mid-static ducted lgred system
Table of Contents

Advertisement

Planning for Snow and Ice, continued.
CAUTION
When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost cycle will not accumulate and freeze on
sidewalks or driveways, which will create unsafe conditions. Properly install and insulate any drain hoses to prevent the hose from freezing, cracking,
leaking, and causing unsafe conditions from frozen condensate.
NOTE
Choose an area where run-off water from defrost cycle will not accumulate and freeze on sidewalks or driveways. Properly install and insulate any
drain hoses to prevent the hose from freezing, cracking, leaking, and damaging the outdoor unit.
The indoor unit will take longer to provide heat, or heating performance will be reduced in winter if the unit is installed:
1. In a narrow, shady location.
2. Near a location that has a lot of ground moisture.
Tie-Downs and Lightning Protection
Tie-Downs
• The strength of the roof must be checked before installing the
outdoor units.
• If the installation site is prone to high winds or earthquakes, when
installing on the wall or roof, securely anchor the mounting base
using a field-provided tie-down configuration approved by a local
professional engineer.
• The overall tie-down configuration must be approved by a local
professional engineer.
Always refer to local code when using a wind restraint system.
Lightning Protection
• To protect the outdoor unit from lightning, it must be placed within
the specified lightning safety zone.
Table 7:
Building Height (feet)
• Power cable and communication cable must be installed five (5) feet away from lightning rod.
• A high-resistance ground system must be included to protect against induced lightning or indirect strike.
NOTE
If the building does not include lightning protection, the outdoor unit will be damaged from a lightning strike. Inform the customer of this possibility in
advance.
GENERAL INSTALLATION GUIDELINES
66
98
148
197
55
45
35
25
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

Outdoor Unit Location Selection

3. In a highly humid environment.
4. In an area in which condensate does not drain properly.
Figure 3: Lightning Protection Diagram.
Lightning rod
Lightning rod
5 feet
Safe zone
Ground
15