PRE-COMMISSIONING
Setting the Optional Modes
Central Control Connection at the
Indoor Units (Fn19)
Central Control Connection function allows the field connection of
the LG AC EZ central controller to the indoor unit communications
bus on Multi V 5 systems.
For use on both heat pump and heat recovery systems.
AC EZ controller was discontinued in the U.S. market January 2016.
Table 57: Setting the Central Control Connection Function.
Settings
Connecting Central Control at IDU Terminals
oFF (Default)
on
AC EZ Connected to the Indoor Unit
Power Consumption Display (Fn21)
The function tells the outdoor unit (master outdoor unit if a multi-
frame system) that power consumption should be monitored. The
function also communicates to the outdoor unit if it will be respon-
sible for reporting the data to the central control device(s), or if an
(optional) LG Power Distribution Integrator (PDI) will be responsible
for reporting.
When the optional PDI is installed, the PDI will monitor outdoor unit
power consumption. PDI allocates outdoor unit power consumed to
indoor units based on the volume of refrigerant flow through each
indoor unit during the billing period.
Power consumption data can then be viewed using an LG ACP or
AC Smart central controller, LG MultiSite Communications Manager,
and LG zone controllers. For installations where a third-party BMS
system is present, consumption data is also made available for
through LG's BACnet Gateway.
For use on both heat pump and heat recovery systems.
Table 56: Setting the Power Consumption Function.
Settings
oFF (Default)
Pd10
Outdoor Unit Assigned Reporting Duty
Pd11
PDI Installed and Assigned Reporting Duty
132
Not Allowed
Communications Bus
Power Monitoring
No Power Monitoring
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Setting the Central Control Connection at the Indoor Units.
Turn No. 5 on the master outdoor unit PCB
DIP switch bank SW01 to ON.
Select the "Func" mode by using the SW03C forward ►button and the
SW02C backward ◄ button, and then press the SW01C confirm
Select the "Fn19" function by using the SW03C forward ►button and
the SW02C backward ◄ button, and then press the SW01C
confirm ● button.
Select from "oFF" or "on" options by using the SW03C forward
►button and the SW02C backward ◄ button, and then press
the SW01C confirm ● button.
The Central Control Connection at the Indoor Units function is set.
PCB does not need reset.
Setting the Power Consumption Display Function.
Turn No. 5 on the master outdoor unit PCB
DIP switch bank SW01 to ON.
Select the "Func" mode by using the SW03C forward ►button and the
SW02C backward ◄ button, and then press the SW01C confirm
Select the "Fn21" function by using the SW03C forward ►button and
the SW02C backward ◄ button, and then press the SW01C
confirm ● button.
Select from oFF, "Pd10," or "Pd11" options (see table) by using the
SW03C forward ►button and the SW02C backward ◄ button,
and then press the SW01C confirm ● button.
The Power Consumption Display function is set.
PCB does not need reset.
● button.
● button.