ELECTRICAL

Communication Cable Specifications
Between Multiple Indoor Units
Operating as a Group (Group
Control)
If any indoor units were specified to operate in unison:
• Before running cable, decide which indoor unit will be the "Mas-
ter." The other indoor units in that group will be designated as
"Slave(s)." The zone controller will be connected to the "Master."
• Set the pertinent DIP switch at each indoor unit to identify the
Master and Slave(s). On wall mounted indoor unit models, set the
assignment using the handheld remote controller.
• Use a daisy chain configuration and connect all of the group's
indoor units together starting at the "Master" unit.
NEVER splice, cut, or extend cable length with field provided
cable. Always include enough cable to cover distance between all
components.
For indoor units with hardwired connections SIG - 12V -
GND (Comm.) terminals:
• From the controller to the master indoor unit, use 22 AWG,
3-conductor, twisted, stranded, unshielded. All wiring must comply
with all applicable local and national codes.
• From the master indoor unit to the slave indoor unit(s), daisy chain
using 22 AWG, 3-conductor, twisted, stranded, unshielded
(
Do not attach wire to 12VDC terminal to the slave indoor
units). All wiring must comply with all applicable local and national
codes.
For indoor units with CN-REMO connections:
Use Group Control Kit (sold separately) containing extension and
Y-splitter cables. Use one (1) group control cable kit for each indoor
unit in the group except for the last indoor unit.
• Cable connected to zone controller is the factory default connection.
• Indoor unit connections depend on indoor unit type.
110
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Example of Indoor Unit Group to Zone Controller
Connections (Sig-12V-GND [Comm.] Terminal).
Master Indoor Unit
Signal
12VDC Comm.
Signal
4
5
6
Signal
12VDC Comm.
Example of Indoor Unit Group to Zone Controller
Connections (CN-REMO).
Indoor Unit
Master Indoor Unit
CN-REMO
CN-REMO
LG
Supplied
LG Supplied Group Control Kit (PZCWRCG3)
Indoor Unit
Indoor Unit
Signal
12VDC Comm.
12VDC Comm.
Indoor Unit
CN-REMO