Carrier 3V VVT 33ZCVVTZC-01 Installation And Start-Up Instructions Manual page 57

Pressure dependent control zone controller
Hide thumbs Also See for 3V VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

,,11
,ii
DCVD = 0
3V
TM
Zone Controller DCV Damper Control Logic
DCV
DCVSP
--
DCVD
--
MAXOUT
--
NO
YES
YES
mode?
I Error = DCVSP
- DCV
1
I,ote0_ol
T ..... _E . .... ,oteg_, Going+
Previo_s,nteg_olTerm
I
1
I
I
IProportional
Term = Error x Proport{onal
Gain
I
1
I
DCVD = Proportional
Term + Integral
Term + Starting
Value
1
IPrevious
Term =
Term
Integral
Integral
LEGEND
Demand Control Ventilation Sensor
Demand Control Ventilation Setpoint
Demand Control Ventilation Damper Output
DCVD Configured
Maximum Output
DCVD=
MAXOUT
57