Carrier 3V VVT 33ZCVVTZC-01 Installation And Start-Up Instructions Manual page 46

Pressure dependent control zone controller
Hide thumbs Also See for 3V VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

Table 19-
System Commissioning
Maintenance Table
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
Commissioning
Mode
Disable
Enable/Disable
SCMOD
Auto-Disable
Timer
0.0
Min
SCTIME
All Zone Dampers
to Max
Disable
Enable/Disable
ZD_MAX
All Zone Dampers
to Min
Disable
Enable/Disable
ZD_MIN
Position
Single
Zone
Disable
Enable/Disable
ZD_SING
Zone 1 Damper Position
0
%OPEN
ZD_POS0!
Zone 2 Damper Position
0
%OPEN
ZD_POS02
Zone 3 Damper Position
0
%OPEN
ZD_POS03
Zone 4 Damper Position
0
%OPEN
ZD_POS04
Zone 5 Damper Position
0
%OPEN
ZD_POS05
Zone 6 Damper Position
0
%OPEN
ZD_POS06
Zone 7 Damper Position
0
%OPEN
ZD_POS07
Zone 8 Damper Position
0
%OPEN
ZD_POS08
Zone 9 Damper Position
0
%OPEN
ZD_POS09
Zone 10 Damper Position
0
%OPEN
ZD_POS 10
Zone 11 Damper Position
0
%OPEN
ZD_POS1 !
Zone 12 Damper Position
0
%OPEN
ZD_POS 12
Zone 13 Damper Position
0
%OPEN
ZD_POS13
Zone 14 Damper Position
0
%OPEN
ZD_POS14
Zone 15 Damper Position
0
%OPEN
ZD_POS15
Zone 16 Damper Position
0
%OPEN
ZD_POS 16
Zone 17 Damper Position
0
%OPEN
ZD_POS 17
Zone 18 Damper Position
0
%OPEN
ZD_POS 18
Zone 19 Damper Position
0
%OPEN
ZD_POS 19
Zone 20 Damper Position
0
%OPEN
ZD_POS20
Zone 21 Damper Position
0
%OPEN
ZD_POS21
Zone 22 Damper Position
0
%OPEN
ZD_POS22
Zone 23 Damper Position
0
%OPEN
ZD_POS23
Zone 24 Damper Position
0
%OPEN
ZD_POS24
Zone 25 Damper Position
0
%OPEN
ZD_POS25
Zone 26 Damper Position
0
%OPEN
ZD_POS26
Zone 27 Damper Position
0
%OPEN
ZD_POS27
Zone 28 Damper Position
0
%OPEN
ZD_POS28
Zone 29 Damper Position
0
%OPEN
ZD_POS29
Zone 30 Damper Position
0
%OPEN
ZD_POS30
Zone 31 Damper Position
0
%OPEN
ZD_POS31
Zone 32 Damper Position
0
%OPEN
ZD_POS32
Bypass Damper Position
0
%OPEN
BDP
Bypass
Pressure
Sensor
0.00
in H20
BPSENS
Bypass Pressure Setpoint
0.00
in H20
BPSETP
AUTO DISABLE
TIMER -- This vmiable displays the num-
ber of minutes
remaining
before
the system commissioning
mode will be automatictflly
disabled.
System commissioning
mode is automatic_dly disabled after one hour of no activity in
this table. The Auto Disable Timer is reset each time a v;due is
changed in this table.
Auto Disable
Timer:
Display Range
0 to 60 min
Network Access
None
ALL ZONE
DAMPERS
TO MAX -- This variable displays
whether
the Linkage
Coordinator
zone controller
has been
directed to set all of its linked zone controllers
to their config-
ured Cool Maximum
Positions (Dmnper Service Configuration
Table). If this decision is forced to Erlable, the Linkage Coordi-
nator zone controller
will set all system zone dampers to their
configured
Cool Maximum
Positions
and display the values in
Zone (1-32) Damper Position
variables. At this time if any of
the Zone (1-32) Damper Position variables are forced, the new
position will be written to the zone's Cool Maximum
Position
and Heat Maximum
Position configuration
values and the zone
will be repositioned
to this new maximum
position.
NOTE: If this zone controller
is not the Linkage Coordinator,
enabling
this variable will have no effect.
All Zone
Dampers to Max:
Display Range
Enable/Disable
NetwoN
Access
Read/Write
ALL ZONE DAMPERS
TO MIN -- This vmiable
displays
whether
the Linkage
Coordinator
zone controller
has been
directed to set all of its linked zone controllers
to their config-
ured Cool Minimum
Positions
(Damper Service Configuration
Table). If this decision is forced to Erlable, the Linkage Coordi-
nator zone controller
will set all system zone dampers to their
configured
Cool Minimum
Positions and display the values in
Zone (1-32) Damper Position
vmiables. At this time if tiny of
the Zone (1-32) Damper Position variables are forced, the new
position will be written to the zone's Cool Minimum
Position
and Heat Minimum Position configuration
values and the zone
will be repositioned
to tiffs new minimum
position.
NOTE: If this zone controller
is not the Linkage Coordinator,
enabling
this variable will have no effect.
All Zone
Dmnpers to Min:
Display Range
Enable/Disable
NetwoN
Access
Read/Write
46