Carrier 3V VVT 33ZCVVTZC-01 Installation And Start-Up Instructions Manual page 54

Pressure dependent control zone controller
Hide thumbs Also See for 3V VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

The zone controller can be configured
for one of three types
of air terminal control - single duct, series fan or parallel fan. If
configured
for parallel fan, the fan will be energized
whenever
the there is a demand
for heat the system mode is not Heating
and when there is a demand for heat when the zone is unoccu-
pied and the system mode is not Heating.
If configured
for
series fan, the fan will be energized
whenever
the zone is
occupied
and when the there is a demand
for heat when it is
unoccupied.
To prevent all series ftm zones fiom starting tit one
time, the zone controller will run a start delay algorithm
based
on the zone controllers
address to stagger the fan stm't time.
Before starting the fan is started the zone dmnper will go to the
fully closed
position
to prevent
the fan from stm'ting back-
wards. The following
formula
is used to delay the fan start in
second:
Delay time in seconds
= (((Whole
Remainder
of Element#/
20)*60)+20)
ZONE DAMPER
TEMPERATURE
CONTROL
--The
damp-
er will modulate to adjust the airflow to the space to mtfintain
its current set point. The damper is controlled
by a PID loop to
provide
plecise
control of the damper
position.
The damper
will be modulated
opened if the system mode and local mode
are the stone. As the zone temperature
gets closer to the set
point, the damper
will modulate
to the Minimum
Dmnper
Position.
The amount the damper
will be open at any given
time depends
on how far away the temperature
is from the set
point, how fast it takes to satisfy the mode, and the Minimum
and Maximum
Positions
for current mode. Once the zone is
satisfied the damper will go to its Minimum
Damper Position
for that mode. Cool/Heat
Minimum
and Maximum
Positions
me defined in the Damper selwice configuration
table.
If the local zone temperatme
is different
fiom the system
mode then the damper
will be at Minimum
Position
for the
system mode.
ZONE
DAMPER
REHEAT--
If the
zone
controller
has
optional
reheat instt_lled, it will use this heat to maintain
the
heating set point. There am 4 types of heat options available as
listed below:
Modulating
hot water
or steam
(requires
a supply
air
temperature
[SATI
sensor
for ducted
heat or a leaving
water temperature
sensor for baseboard
heat)
Two-position
hot water or steam (SAT required)
1 to 3 stages of electric
heat (SAT required)
Combination
of staged baseboard
and ducted
heat (SAT
required)
If the zone controller is configured
for single duct terminal,
the system mode is cooling, and the zone local mode is heating
the damper will go to the configured Reheat Minimum
Position
or the Cool Minimum
Damper Position
(as configured
in the
Damper service configuration
table) whichever
is greatel: and
reheat will be energized.
If the zone controller
is configured
for series or parallel fan
terminal the zone controller
will close the dmnper to the Cool
Minimum
Position
before energizing
the reheat. For parallel
zone termimds
the fan will be energized
as the first stage of
heat. The zone controller
uses a PID algorithm
to calculate
a
supply air or leaving water temperature,
which the reheat will
be controlled
to, in order to satisfy the heat demand.
If the system mode is Heating, the zone controller will try to
heat the zone with the central heat but may energize leheat to
satisfy the demand if it is required. If the terminal type is con-
figured for pm'allel fan the fan will lem_in off. If no reheat
is desired
in the zone while central heat is on or under any
other specific conditions,
it can be disabled by forcing the Heat
point in the Status Display table to Disable. Contact your local
Cturier Controls representative
if you need assistance
with this
application.
ZONE
DAMPER
VENTILATION
-- After the zone has sat-
isfied and the system mode is Cooling or Free Cooling and the
SAT is between 65 and 75 E the damper will go to its Ventila-
tion Position
or the Cool Minimum
Position,
whichever
is
greatel: If the SAT is less then 65 or greater
then 75 or the
system mode changes to Heating, the damper go to the current
system
mode Minimum
Position.
The
Ventilation
Damper
Position is defined in the Dmnper service configuration
table.
DEMAND
CONTROL
VENTILATION
(DCV) --If
the zone
controller has a CO 2 Demand Ventilation
sensor it will be able
to override the temperature controlled
dmnper position if it is
occupied,
the system mode is Cooling or Free Cool, and the
zone is does not have a demand for heat. When the IAQ sensor
exceeds the configured
Demand Vent set point it will use a PID
algorithm
to calculate a higher damper position to _llow more
airflow
to the zone in order to dilute the
CO
2
levels. The
Demand
Ventilation
algorithln
has a higher
priority then the
temperature
control algorithm
under these conditions
so the
damper will be controlled
to the greater of the two values. The
DCV mode, when active, overrides
the Cool Minimum
and
Ventilation
Positions.
As the CO 2 levels decrease
in the zone
the damper
will
soon be returned
to normtd
temperature
control.
If the zone is configured
for modulating
ducted reheat and
the zone temperature
decreases
to less than half way between
the heat and cool set point then the reheat will be enabled to
prevent the zone fi_m going into the heat mode. If the zone is
configured
for any other type of reheat it will NOT be ener-
gized. If the temperature
continues to decrease
below the heat
set point, the DCV mode will be disabled and the zone will re-
sume normal temperature
control.
The zone ZNMAINT
maintenance
status table will display
the calculated
dmnper position and if the temperature
or DCV
is in control of the damper as well as other information
such as
occupancy
status, heat and cool set points, reheat sub-master
reference and whether local heating or cooling is in effect.
LOADSHED
-- The zone controller
can respond to a redline
or loadshed
broadcast
fi_m an optional
Loadshed
module
in-
stalled on the Carrier communicating
netwoN.
The purpose of
this function is to monitor and conserve
electrical power usage.
If a redline command
is broadcast
the zone controller
expand
its heat and cool set points by the mnount that is configured
in
Loadshed Offset Adjust decision in the OPTIONS
service con-
figuration
table. The default is 2 ° F so this amount
would be
subtracted
from the heat set point and added to the cool set
point if is left unchanged.
A configurable
mdline/loadshed
de-
lay timer (Maximum
Ix_adshed Time decision in the OPTIONS
service configuration)
will also stmted to prevent the set points
from being expanded indefinitely.
If a Ixmdshed command
is broadcast then the set points will
be expanded and the zone controller will drop 1 stage of reheat
providing
that the reheat option is enabled and there is more
than one stage of heat. The set points will be returned to normal
and additional
staged heat will be _dlowed when the redline/
loadshed
command
is ctmceled by the Ixmdshed
Module, the
zone controller's
internal
redline/loadshed
delay timer times
out or the zone
becomes
unoccupied.
Contact
your local
C_urier Controls
representative
for more information
on this
application.
54