Table 18 --Time
Schedule Maintenance Table
DESCRIPTION
VALUE
UNITS
NAME
Mode
1
MODE
Current
Occupied Period
2
PERIOD
Override
in Progress
No
OVERLAST
Override Duration
0
min
OVERDURA
Occupied
Start Time
08:00
OCCSTART
Unoccupied
Start Time
18:00
UNSTART
Next Occupied
Day
Thu
NXTOCCD
Next Occupied
Time
00:00
NXTOCCT
Next Unoccupied
Day
Wed
NXTUNOD
Next Unoccupied
Time
18:00
NXTUNOT
Last Unoccupied
Day
PRVUNOD
Last Unoccupied
Time
00:00
PRVUNOT
UNOCCUPIED
START
TIME -- This variable displays the
time that the current occupied
mode will end (the beginning
of
the next unoccupied
mode).
Unoccupied
Start
Time:
Display Range
00:00 to 24:00
Network Access
None
NEXT OCCUPIED
DAY-
This vadable
displays
the &ty
when the next occupied
period
is scheduled
to begin. This
point is read in conjunction
with the next occupied
time to
allow the user to know the next time and day when the next
occupied period will occm:
NOTE: If the current mode is occupied, this point makes refer-
ence to the next occupied
pedod
and, in most cases, may not
be the stone as the cunent occupied
start time.
Next Occupied
Day:
Display Range
MON, TUE, WED,
THU, FRI, SAT. SUN
Network Access
None
NEXT OCCUPIED
TIME -- This variable displays the time
of day when the next occupied
period will occm: This point is
read in conjunction
with the next occupied
&ty to allow the
user to know the next time and day when the zone will become
occupied.
NOTE:
If the current
mode is occupied,
this point makes
reference
to the next occupied
period
and, in most cases,
may not be the same as the current occupied
start time.
Next Occupied
Time:
Display Range
00:00 to 24:00
Network Access
None
NEXT UNOCCUPIED
DAY--
This
variable
displays
the
day when the next unoccupied
period is scheduled
to begin.
This point is read in conjunction
with the next unoccupied
time
to allow the user to know the next time and day when the zone
will become unoccupied.
NOTE:
If the current
mode is unoccupied,
this point makes
reference
to the next unoccupied
period and, in most cases,
may not be the same as the current unoccupied
start time.
Next Unoccupied
Day:
Display Range
MON, TUE, WED,
THU, FRI, SAT. SUN
Network Access
None
NEXT UNOCCUPIED
TIME -- This variable
displays
the
time of day when the next unoccupied
period
is scheduled
to begin.
This
point is read in conjunction
with the next
unoccupied
day to allow the user to know the next time and
&ty when the zone will become unoccupied.
NOTE:
If the current mode is unoccupied,
this point makes
reference
to the next unoccupied
period and, in most cases,
may not be the same as the current unoccupied
start time.
Next Unoccupied
Time:
Display Range
00:00 to 24:00
Network Access
None
LAST UNOCCUPIED
DAY--
This
vmiable
displays
the
last day when the zone changed from occupied to unoccupied
mode. This point is read in conjunction
with the last unoccu-
pied time to allow file user to know the last time and day
when the zone became unoccupied.
Last Unoccupied
Day:
Display Range
MON, TUE, WED,
THU, FRI, SAT. SUN
Network Access
None
LAST UNOCCUPIED
TIME -- This
variable
displays
the
last time of &ly when the zone changed from occupied to unoc-
cupied mode. This point is read in conjunction
with the last
unoccupied
day to _dlow the user to know the last time and day
when a zone becmne unoccupied.
Last Unoccupied
Time:
Display Range
00:00 to 24:00
Network Access
None
System
Commissioning
Maintenance
Table --
The System Colnmissioning
Maintenance
_tble (SYSTCOMM)
displays and perlnits the setting of 'all &tlnpel_ in the linked sys-
tem from the Linkage Coordinator
zone controllel: The bypass
controller
&tmper position,
system plessme
and pressure
set
point me also displayed and the plessure set point may be _dteled
directly from fllis table. See Table 19.
COMMISSIONING
MODE
-- This vmiable is used to put
file master zone controller
into the commissioning
mode. Force
tiffs point to enable. The Linkage Coordinator
zone controller
will be ready to accept a command
to perform the tests and
functions
on this screen. The Linkage Coordinator
zone con-
troller will go into ZONE_BAL
mode.
NOTE:
If this zone controller
is not the Linkage Coordinatol:
enabling
this variable will have no effect.
Commissioning
Mode:
Display Range
Disable/Enable
Default Value
Disable
Network Access
Read/Write
45