AIRSOURCE BUS ANDELEMENT NUMBER - - TheAir
Source B usandElement Number configurations
define the
address ofthe airsource providing conditioned
airtothe zones
controlled bythelinkage c oordinatol:
If theaddress is leftat
zero, thelinkage coordinator
willlookforaprimal"/air sensor
todetermine theequipment
mode. If noprimal"/air sensor is
installed, or thesensor fails,theLinkage C oordinator will
default the airsource mode t oCooling.
AirSource
Bus Number: Range
0 to239
Default Value 0
AirSoume
Element Number: Range
0to239
Default Value 0
Table 7 -- Damper Service Configuration
Table
DESCRIPTION
VALUE
UNITS
NAME
Cool Minimum Pos
0
%
CMINPOS
Cool Maximum Pos
100
%
CMAXPOS
Reheat Minimum Pos
0
%
REMINPOS
Heat Minimum Pos
0
%
HMINPOS
Heat Maximum Pos
100
%
HM_POS
Ventilation Pos
30
%
VENTPOS
Table 8 -- Holiday Configuration
Table
DESCRIPTION
VALUE
UNITS
NAME
Start Month
1
MONTH
Start Day
1
DAY
Duration
0
DURATION
Table 9 -- Linkage
Configuration
Table
DESCRIPTION
VALUE
UNITS
NAME
Zone Linkage
Linkage Master Zone
No
MAST_ENA
Number of Zones
1
NUM_ZONE
Air Source
Bus #
0
AS_BUS
Air Source
Element #
0
AS_ELEM
System
Bypass Exists
Yes
SYS_BP
SAT Mode Verification
No
SAT_CHCK
Supply
Air Location
0
SAT_LOC
0 = Airsource
1 = Local PAT
2 = Bypass
CCN-LINKAGE
DATA
CCN Variable Name
CCNVAR
CCN Func Config
0
CCNFUNC
0 = None
1 = Average
2 = Low
3 = High
Data Transfer
Rate
10
rain
DATARATE
CCN Output
Point
CCNOUTP
Destination
Bus #
0
DESTBUSN
Destination
Element #
0
DESTELEN
TEMP SENSOR GROUPING
Sensor Mode
1
BRD_RECV
1 = Local Sensor
2 = Broadcast
3 = Listen
Listen Sensor Config
1
SENSCFG
1 = SPT
2 = SPT & Offset
Broadcasting
Element #
1
BRDDEVID
34