Carrier 3V VVT 33ZCVVTZC-01 Installation And Start-Up Instructions Manual page 31

Pressure dependent control zone controller
Hide thumbs Also See for 3V VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

Table 6 -- Terminal Service Configuration Table
DESCRIPTION
VALUE
UNITS
NAME
COOLING
Terminal
Type
1
TERMTYPE
1 = Single Duct
2 = Parallel Fan
3 = Series Fan
Primary
Inlet Size
Inlet Diameter
(Inches)
6.0
RND_SIZE
Inlet Area (Sq. In.)
0.0
SQ_AREA
Damper PID
Proportional
Gain
10.0
KP
Integral
Gain
2.5
KI
Derivative
Gain
4.0
KD
Starting
Value
40.0
%
STA RTVAL
CW Rotation
Close
DMPDIR
HEATING
Heat Type
0
H EATTYPE
0 = None
2 = Two Position
3 = Staged Electric
4 = Modulating/CV
5 = Combination
Heating
PID
Proportional
10.0
KP
Integral
Gain
0.5
KI
Derivative
Gain
0.0
KD
Starting
Value
80.0
dF
STA RTVAL
Ducted
Heat
Yes
DUCTHEAT
Maximum
Temperature
110
dF
MAXTEMP
# Electric
Heat Stages
3
STAGES
Heat On Delay
2
min
H©NDEL
Fan Off Delay
2
rain
FOFFDEL
2-Pos Heat Logic
Normal
HEATYPE
System Call for Heat?
Yes
HEATCALL
Supp. Heat Lockout
Temp.
140.0
dF
SHL_TEMP
System
Pilot Averaging
0
SENS_AVG
0 = System Pilot only
1 = with one T55
2 = with four T55s
3 = with nine T55s
SPT Sensor Trim
0.0
^F
SPT_TRIM
SAT Sensor Trim
0.0
^F
SAT_TRIM
Local SAT Installed
Yes
LOC_SAT
Remote Contact
Config
Close
RMT_CFG
3!