3210 Timer Setting Procedure - Pentair FLECK 2815 Service Manual

Water softener or filter control valve
Table of Contents

Advertisement

3210 TIMER SETTING PROCEDURE

Typical Programming Procedure
Calculate the gallon capacity of the system, subtract the
necessary reserve requirement and set the gallons available
opposite the small white dot on the program wheel gear
(Figure 54).
NOTE: Drawing shows 8,750 gallon setting. The capacity
(gallons) arrow (15) shows zero gallons remaining.
The unit will regenerate tonight at the set
regeneration time.
How To Set The Time Of Day
1. Press and hold the red button in to disengage the drive
gear.
2. Turn the large gear until the actual time of day is opposite
the time of day pointer.
3. Release the red button to again engage the drive gear.
How To Manually Regenerate Your Water Conditioner At
Any Time
NOTE: Always remove the meter cable from the meter cap
before opening the timer door.
1. Turn the manual regeneration knob clockwise.
2. This slight movement of the manual regeneration knob
engages the program wheel and starts the
regeneration program.
3. The black center knob will make one revolution in the
following approximately three hours and stop in the
position shown in the drawing.
4. Even though it takes three hours for this center knob to
complete one revolution, the regeneration cycle of your
unit might be set for only a portion of this time.
5. In any event, conditioned water can be drawn after the
rapid rinse cycle has completed or no water is flowing out
the drain line.
NOTE: The program wheel in Figure 4 may be different than
the program wheel on the product.
NOTE: To set meter capacity rotate manual knob one - 360°
revolution to set gallonage.
NOTE: Immediate regeneration timers do not have a
24-hour gear. No time of day can be set.
Figure 5
61502-3200 Rev A
FLECK
2815 Control Valve Service Manual
• 7