Operating Area - Kalor Denia 14 Installer And User Manual

Table of Contents

Advertisement

Operating area

For proper functioning and a good temperature distribution,
the stove shoul be positioned in a location where it is able
to take in the air necessary for combustion of the pellet
(about 40 m
/h must be available, as laid down in the
3
standard governing the installation and in accordance with
local national standards).
The volume of the room must not be less than 30 m
The air must come in through permanent openings made
in walls (in proximity to the stove) which give onto the
outside, with a minimum cross-section area of 100 cm
These openings must be made in such a way that it is not
possible for then to be obstructed in any way. Alternatively,
the air can be taken from rooms adjacent to the one which
needs ventilating, as long as they are provided with an air
intake from the outside, and are not used as bedrooms or
bathrooms, and provided there is no fire risk such as there
is for example in garages, woodsheds, and storerooms,
with particular reference to what is laid down in current
standards.
It is not permissible to install the stove in
bedrooms, bathrooms, or in a room where
another heating appliance is installed
(fireplace, stove etc.) which does not have its own
independent air intake.
Locating the stove in a room with an explosive
atmosphere is prohibited.
The floor of the room where the stove is to be
installed must be strong enough to take its weight. If
walls are flammable, maintain a minimum distance
of 20 cm at the rear (A), of 30 cm at the side (B) and
100 cm at the front. If the room contains objects
which are believed to be particularly delicate, such
as drapes, sofas and other furniture, their distance
from the stove should be considerably increased.
If the stove is installed on a flammable
floor it must be interposed with a slab of
insulating material to heat it protrudes at
least 20 cm on the sides and 40 cm on the
front.
Connection to the external air intake
It is essential that at least as much air must be able to flow
into the room where the stove is installed as is required for
proper combustion in the appliance and for the ventilation
of the room. This can be effected by means of permanent
openings in the walls of the room to be ventilated, which
give onto the outside, or by single or collective ventilation
ducts.
For this purpose, on the external wall near the stove, a
hole must be made with a minimum free cross-section of
100 cm
. (equivalent to a round hole of 10 cm diameter or
2
a square hole 10x10 cm) protected by a grille on the inside
and the outside.
32
.
3
.
2
The air intake must also:
• communicate directly with the room where the stove is
installed
• be protected by a grille, metal mesh or suitable guard, as
long as this does not reduce the area below the minimum.
• positioned in such a way as to be impossible to obstruct.
In the presence of wood floors, install a
floor protection surface in compliance
with the rules in force in the country
20 cm (A)
Min.
100 cm
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mia 16Denia 14dMia 16d

Table of Contents