INSTALLATION

TURN THE POWER OFF AT THE CIRCUIT BREAKER
BEFORE INSTALLING THE SENSOR OR WORKING ON THE LOAD.
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the DSW flying leads as shown in the wiring diagram below
that is appropriate to the DSW model and electrical supply.
3. Attach the DSW to the wall box by inserting
screws into the two wide holes on the top
and bottom of the attached metal bracket.
Match them up with the holes in the wall
box and tighten.
4. Turn the circuit breaker ON. Wait one
minute, then push the ON/OFF button for
each load and the lights will turn ON.
5. Test and adjust the sensor if necessary.
6. Attach the cover plate.
Neutral
Line
Black
Blue
Neutral
White
Ground
Green
DSW-200
Bi-Level Wiring
Visit our website for FAQs: www.wattstopper.com
WARNING
White
Primary
Red
Load
Brown
Secondary
Load
#12 — #14 AWG
Cu Wire Only
Neutral
Line
Black
Neutral White
Ground
Green
DSW-100 Wiring
Neutral
Line 1
Black
Line 2
Blue
Neutral
White
Ground
Green
Neutral
DSW-200
Dual Circuit Wiring
Strip Gage
1/2"
12.7mm
Load
Red
White
Red
Primary
Load
Brown
Secondary
Load
White