Appendix I - Venting size data
SSB 800 SA
CO
2
Exhaust gas mass (weight)
Flue temperature
Max. pressure at boiler exit
SSB 1000 SA
CO
2
Exhaust gas mass (weight)
Flue temperature
Max. pressure at boiler exit
SSB 1000 TL
CO
2
Exhaust gas mass (weight)
Flue temperature
Max. pressure at boiler exit
SSB 1000 TL2
CO
2
Exhaust gas mass (weight)
Flue temperature
Max. pressure at boiler exit
SSB 1000 TL3
CO
2
Exhaust gas mass (weight)
Flue temperature
Max. pressure at boiler exit
SSB 1000 TL4
CO
2
Exhaust gas mass (weight)
Flue temperature
Max. pressure at boiler exit
SSB
T supply / return (°F): 176 / 140
Unit
Maximum Input
%
9
lb/s
0,21
°F
167
in. wc
0,83
T supply / return (°F): 176 / 140
Unit
Maximum Input
%
9
lb/s
0,26
°F
176
in. wc
0,91
T supply / return (°F): 176 / 140
Unit
Maximum Input
%
9
lb/s
0,26
°F
176
in. wc
0,96
T supply / return (°F): 176 / 140
Unit
Maximum Input
%
9
lb/s
0,53
°F
176
in. wc
0,91
T supply / return (°F): 176 / 140
Unit
Maximum Input
%
9
lb/s
0,79
°F
176
in. wc
0,79
T supply / return (°F): 176 / 140
Unit
Maximum Input
%
9
lb/s
1,06
°F
176
in. wc
0,59
T supply / return (°F): 104 / 86
Minimum Input
Maximum Input
9
9
0,02
0,21
147,2
104
0,04
0,72
T supply / return (°F): 104 / 86
Minimum Input
Maximum Input
9
9
0,02
0,26
152,6
104
0,05
0,83
T supply / return (°F): 104 / 86
Minimum Input
Maximum Input
9
9
0,02
0,53
152,6
104
0,05
0,86
T supply / return (°F): 104 / 86
Minimum Input
Maximum Input
9
9
0,02
0,53
152,6
104
0,05
0,82
T supply / return (°F): 104 / 86
Minimum Input
Maximum Input
9
9
0,02
0,79
152,6
104
0,05
0,71
T supply / return (°F): 104 / 86
Minimum Input
Maximum Input
9
9
0,02
1,06
152,6
104
0,05
0,51
VENTING SIZE DATA | 57
Minimum Input
9
0,02
89,6
0,03
Minimum Input
9
0,02
91,4
0,03
Minimum Input
9
0,02
91,4
0,03
Minimum Input
9
0,02
91,4
0,03
Minimum Input
9
0,02
91,4
0,03
Minimum Input
9
0,02
91,4
0,03
6720866942 (2018/06) US