Condensate Drain And Piping; Electrical Connection - Bosch SSB800 SA Installation And Service Instructions For Contractors

Gas condensing stainless steel boiler, buderus ssb boiler
Hide thumbs Also See for SSB800 SA:
Table of Contents

Advertisement

4 .4 .7

Condensate drain and piping

The SSB boiler is designed to condense water vapor from the flue
products. Each module of the boiler is equipped with a condensate drain
system (see Fig. 18), connected to the condensate horizontal manifold.
Horizontal
Condensate
Manifold
Condensate
Syphon
Fig. 18 Condensate Drain System
WARNING: At the Start-up and after prolonged shutdown
a
of the boiler, the syphon must be filled with water prior to
restart it, otherwise combustion gases will enter the room
with a risk of an excessive level of carbon monoxide.
The procedure for filling the traps and syphon with water is shown on the
Fig. 19:
Disconnect the
condensate pipe
Fill the syphon
with water
Fig. 19 Water Filling of Condensate System
SSB
• The installation must have provisions for suitable drainage or
collection of the condensate out of the boiler traps.
• The condensate water shall be discharged at atmospheric pressure,
by dripping into a suitable drain, and shall be neutralized prior to
draining per local codes.
• The condensate drain tube must pitch away from the boiler (1/4" slope
per foot) and must never reduce its diameter downstream.
• Never use copper pipes or of other material not intended for the
specific purpose, because the action of condensate will cause a rapid
deterioration.
• Check that the condensate drain pipe is adequately sloping towards
the discharge point avoiding high points, which can inhibit the flow of
condensate. The condensate pipe must be installed in such a way so
as to avoid the freezing of the liquid.
WARNING: Verify condensate disposal / neutralization is in
a
accordance with local, state and federal regulations.
If a floor drain is not available, a condensate pump can be used to
remove the condensate to drain. The maximum condensate flow rate is
6.2 GPH for SSB 800 SA and 7.9 GPH for SSB 1000 SA / 1000 TL. The
drain line must be removable for routine maintenance.
CAUTION: Use PVC, CPVC, stainless steel, aluminum or
a
polypropylene for condensate drain piping (Fig. 20). DO
NOT use carbon or copper components.
Relief valves drain
Fig. 20 Condensate Drain and Relief Valves Manifold Locations
4 .4 .8

Electrical Connection

The voltage configuration of SSB 800 SA, 1000 SA and 1000 TL is as
follows:
• 120VAC, 1-Phase, 60 Hz
Each boiler must be connected to a dedicated electrical circuit.
NO OTHER DEVICES SHOULD BE ON THE SAME ELECTRICAL
CIRCUIT AS THE BOILER .
Installation | 19
Condensate drain
6720866942 (2018/06) US

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ssb1000 saSsb1000 tl

Table of Contents