Appendix F - Exhaust Terminals And Air Inlet Clearances - Bosch SSB800 SA Installation And Service Instructions For Contractors

Gas condensing stainless steel boiler, buderus ssb boiler
Hide thumbs Also See for SSB800 SA:
Table of Contents

Advertisement

Appendix F - Exhaust terminals and Air inlet Clearances

3
X
3
Direct vent (sealed combustion) / Fan assisted appliance (Room air for combustion) . See Note 1)
[1] Forced air inlet
[2] Gravity air inlet
[3] Exhaust terminal
X1 1 foot (305 mm)
X2 At least 3 feet (915mm)
X3 1 foot (305 mm) USA - Direct vent (sealed combustion)
4 foot (1220mm) USA - Fan assisted appliance (room air
combustion)
3 feet (915 mm) Canada
It is not recommended to terminate vent above any door or window, condensate can freeze causing ice formations.
Locate vent termination minimum 7' (2.1 m) above any public walkway, with consideration to condensate.
Position termination so it will not be effected by wind eddy, air born leaves, snow, or recirculated vent gases. Give consideration to excessive wind and
locate away from windward side of building.
Do not use chimney as a raceway if another boiler or fireplace is vented into or through chimney.
All CPVC vent pipes must be glued, except for the flue gas adapter pipe connection.
Vent terminations must keep the following minimum clearances from electric meters, gas meters, regulators and relief equipment: 4 feet (1220 mm)
[Canada 6 feet (1830 mm)] horizontally and in no case above and below, unless a horizontal distance of 4 feet (1220 mm) [Canada 6 feet (1830 mm)] is
maintained.
NOTE
1) For Clearances not specified in ANSI Z223.1 / NFPA 54 or CSA B149.1 Clearance in accordance with local installation codes and the requirements of
the gas supplier including the Authority having jurisdiction.
SSB
3
X
3
3
X4 See Note 1)
X5 7 feet (2135 mm)
YA At least 1 foot (305 mm) above grade or snow line
YB Exhaust terminal must be at least:
EXHAUST TERMINALS AND AIR INLET CLEARANCES | 53
X
2
X
2
1
3 feet (915 mm) above forced air inlet within
10 feet (3050 mm) horizontally – USA
6 feet (915 mm) above forced air inlet - Canada
3
2
6720866942 (2018/06) US