LP ORIFICE INSTALLATION (SSB160)
Natural Gas to LP conversion
The heating unit is factory preset for operating with natural gas. This
set-up can be changed using the conversion kits supplied by the
manufacturer.
NOTICE: This change may only be performed by an
authorized Servicing Center, according to the following
procedure.
Converting from NATURAL GAS to LP
► Close the gas cock
► Disconnect the electric power supply from the boiler
WARNING: to avoid electrical shock, it is mandatory to
a
disconnect the boiler from the power supply using a bipolar
external switch..
► Remove the front panel
► Unscrew the 3 screws 'A' and the swivel joint 'B' indicated in Fig. 23 to
separate the valve from the fan
► Separating the two components, you can see the hole where the gas
passes with its gasket
► Insert the provided metal orifice 'C' into the gasket "D" without
removing the gasket itself
Boiler model
Orifice Diameter (mm)
SSB160
6.25
Tab. 3
► Check the condition of the gasket 'E'. Replace if necessary
► Tighten the swivel joint 'B'
► Tighten the 3 screws 'A'
► Switch the main power supply to ON
D
C
A
Fig. 23
IMPORTANT: Make sure there is no heat demand from the
thermostat inputs.
F
► Reopen the gas shut-off cock
► Use the control panel to enter in the parameter list and change the
parameter N° 98 (Gas Type) from "NG" to "LPG"
► Adjust the CO
parameter as explained in chapter "5.7 Adjusting and
2
setting CO
limits"
2
► Affix the gas type label from the gas conversion kit to the appliance
(Fig. 24).
SSB
DIRECT VENT BOILER FOR EITHER DIRECT VENT INSTALLATION OR FOR
INSTALLATION USING INDOOR COMBUSTION AIR
Category
Model
Model no.
Converted to LPG (Propane) with conversion kit X XXX XXX XXX
CO
(max. rate/ min rate)
2
Min. inlet gas pressure
Max. inlet gas pressure
Mainfold pressure
Min. input rate
Max. input rate
Output rate
Minimun relief valve capacity
Altitude
(Refer to installation instruction for higher altitudes)
This boiler was converted on
to
(name and address of organization making this conversion), which accepts
the responsability that this conversion has been properly made.
Fig. 24 Affixing the gas type label
4 .7
a
a
a
E
B
Make sure that the combustion air is not contaminated by:
• Permanent wave solutions;
• Chlorinated waxes/cleaners;
• Chlorine-based swimming pool chemicals;
• Calcium chloride used for thawing
• Sodium chloride used for water softening;
• Refrigerant leaks;
• Paint or varnish removers;
• Hydrochloric acid/muriatic acid;
• Cements and glues;
• Antistatic fabric softeners used in clothes dryers;
• Chlorine-type bleaches, detergents, and cleaning solvents found in
household laundry rooms;
• Adhesives used to fasten building products and other similar products.
In any case to prevent contamination do not connect the suction and
discharge near:
• Dry cleaning/laundry areas and establishments;
• Swimming pools;
• Metal fabrication plants;
• Beauty shops;
• Refrigeration repair shops;
CHAUDIÈRE À ÉVENT DIRECT PUT INSTALLATION AVEC ÈVACUATION
DIRECTE OU AVEC AIR COMBURANT
IV
Catégorie
IV
SSB-512
Modèle
SSB-512
7 738 004 896
Référence
7 738 004 896
Convertie vers LPG (Propane) a vec le kit de conversion X XXX XXX XXX
10,7/10,3 %
CO
( max / min)
10,7/10,3 %
2
1,99 kPa
8,0 in.W. C.
Min. pression d'alimentation en gaz
8,0 in.W. C.
3,23 kPa
13,0 in.W. C.
Max. pression d'alimentation en gaz
13,0 in.W. C.
cfactory set - not adjustable
Pression à la conduite de gaz
cfactory set - not adjustable
30,0 kW
102,360 Btu/hr
Consommation calorifique min.
102,360 Btu/hr
150,0kW
511,800 Btu/hr
Consommation calorifique max.
150,0kW
511,800 Btu/hr
144,0 kW
491,328 Btu/hr
Puissance utile nominal
144,0 kW
491,328 Btu/hr
232,1 kg/hr
511,8 lbs/hr
Capacité minimale de la soupape de sécurité
232,1 kg/hr
511,8 lbs/hr
0-610 m
0-2000 ft
Altitude
0-610 m
0-2000 ft
(Se référ à la notice d'installtion en cas d'altitude plis élevée)
(day - month - year)
Ce appareil a été converti le
(jour- mois- année) en
gas. By
gaz
par
(nome ed adtrsse de l'organisme effectuant cette conversion), qui accepte la
responsabilité de la bonne execution de cette conversion.
X XXX XXX XXX
(2015/04)

Venting and air piping system

WARNING: Do not connect this gas appliance with any
other appliance unless approved by manufacturer.
Failure to comply with this WARNING could result in the
accumulation of carbon monoxide gas which can cause
severe personal injury or death.
WARNING: Do not connect SSB models 85, 120 and 160
to a shared/common or cascade vent system. Each boiler
must have a separate, dedicated vent system.
DANGER: The condensate trap must be filled with water
or combustion gases will enter the room with a risk of an
excessive level of carbon monoxide. For instruction see
section 4.4.7.
NOTICE: DO NOT use PVC for vent piping when using
anti-freeze in the primary circuit of the boiler . Use
CPVC, PP or stainless steel only! .
Installation | 23