Bosch SSB800 SA Installation And Service Instructions For Contractors page 54

Gas condensing stainless steel boiler, buderus ssb boiler
Hide thumbs Also See for SSB800 SA:
Table of Contents

Advertisement

54 | EXHAUST TERMINALS AND AIR INLET CLEARANCES
X
Y
Horizontal venting system (sealed combustion):
X ≥ 4" (102 mm);
Y ≥ 12" (305 mm)
Vent
Air intake
Multiple air and vent vertical termination:
X ≥ 12" (305 mm);
Y ≥ 12" (305 mm)
6720866942 (2018/06) US
Air intake
Y
Vent
X
X
X
Y
Vertical venting system (sealed combustion):
X > 12" (305 mm)
Y = 12" (305 mm) above maximum snow level or at least 24" whichever
is greater
Air intake
Vent
X
Multiple air and vent vertical termination:
X ≥ 12" (305 mm);
Y ≥ 12" (305 mm)
X
Y
Air intake
Vent
Y
SSB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ssb1000 saSsb1000 tl

Table of Contents