Boiler Screen; Module Screen; Performance Screen - Bosch SSB800 SA Installation And Service Instructions For Contractors

Gas condensing stainless steel boiler, buderus ssb boiler
Hide thumbs Also See for SSB800 SA:
Table of Contents

Advertisement

36 | Operation
6 .3 .3

Boiler Screen

Through this screen, the following actions can be done:
• Check the status of the modules (ON, OFF, in error);
• See the current supply temperature at the boiler header;
• Access the Module screen of the desired module, just touching it on
the screen;
Use the side buttons to perform the actions listed below:
• Home button: move back to the BOSCH screen;
• Performance button: move to the Performance screen of the boiler;
• Stats button: not active;
• Errors button: move to the Errors screen;
• Service button: move to Service screen;
• Settings button: move to Settings screen;
• Back button: move to the previous screen.
Fig. 54 Boiler screen
6 .3 .4

Module Screen

Through this screen, the following actions can be done:
• See the current value of many parameters: water supply&return
temperature, flue temperature, water flowrate, fan speed, ionization
current, burner and pump status, any error ON or service required;
Use the side buttons to perform the actions listed below:
• Home button: move back to the BOSCH screen;
• Performance button: move to the Performance screen of the
module;
• Stats button: not active;
• Errors button: move to the Errors screen;
• Service button: move to Service screen;
• MODULE TEST button: move to the Module test screen;
• Reset button: clean any Locking error relevant to the module;
• Back button: move to the previous screen.
6720866942 (2018/06) US
Fig. 55 Module screen
IMPORTANT: When resetting a Locking error of the
a
Managing module, the whole boiler will be switched OFF
and then restarted.
6 .3 .5

Performance Screen

The Control system is able to show the "real time" performance of the
plant, starting from 12 hours before the current time. The screen shows
different information according to the context.
The Cascade Performance screen includes the trend of:
• Current power input;
• Targeted temperature setpoint;
• Current supply temperature.
The Boiler Performance screen includes the trend of:
• Current power input;
• Targeted temperature setpoint;
• Current supply temperature.
The Module Performance screen includes the trend of:
• Current power input;
• Targeted temperature setpoint;
• Current supply temperature.
• Current return temperature;
• Current fan speed;
• Current ionisation current;
• Current flue temperature.
Fig. 56 Service screen
SSB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ssb1000 saSsb1000 tl