When the appliance is installed at an altitude higher than 2000 ft, the fan speed must be set to the top of the available range in any case and a de-rating
of the input capacity must be considered in function of the altitude combined with the total length of the vent and combustion air pipe as reported in the
following table (input BTU/hr):
SSB 800 SA
Altitude (ft)
0-2000
3000
4000
5000
6000
7000
8000
9000
10000
SSB 1000 SA / 1000 TL
Altitude (ft)
0-2000
3000
4000
5000
6000
7000
8000
9000
10000
To calculate the de-rating of the input capacity follow this example:
We have an SSB 1000 SA boiler installed at 5400 ft with a 6" flue system. The equivalent length of the vent pipe installed is 55 ft.
The equivalent length of the air combustion pipe installed is 35 ft.
The total equivalent length of the flue system is 55+35 = 90 ft. The maximum equivalent length for this type of installation is (see IOM manual) 100 ft.
The % range is 90/100 = 90%. This value is within the 75% and 100%.
Now the correct de-rating value is given from the value of the fourth column (From 75% to 100%) of the SSB 1000 SA / 1000 TL table that crosses