14 Mechanical installation
Attention:
•
The wall behind the unit is of non-flammable material.
•
The floor that the unit is installed on is of non-flammable material.
•
The maximum allowed floor flatness deviation from the surface level is 5mm in every 5
meters.
•
Drive minimal distances to the walls:
•
Front side: 1600 mm
•
Rear side: 100 mm
•
Top side: 850 mm
•
Left side: 100 mm
•
Right side: 100 mm
Installation of EC fan units
AC fans are already mounted when delivered from works.
EC fans need to be installed with fan box in the field.
For information on the number of fan units to be installed, see
Drawing.
Installation
1. Lift the fan unit onto the cabinet roof by means of a forklift or a crane (if using a crane,
empty the lifting eyes in the fan roof).
•
~70 kg for EC500 fan units
•
~90 kg for EC560 fan units
NOTICE
The mounting position can be identified by the cutouts in the drive roof.
ACS580MV Outline