Ramps And Brakes Setup (Control Panel: Menu Par -> P4) - Honeywell SmartVFD COMPACT User Manual

Variable frequency drives for constant and variable torque applications
Hide thumbs Also See for SmartVFD COMPACT:
Table of Contents

Advertisement

Honeywell
9.5 RAMPS AND BRAKES SETUP (CONTROL PANEL: MENU PAR -> P4)
Code
Parameter
P4.1
Ramp shape
Acceleration
P4.2
time
Deceleration
P4.3
time
DC braking cur-
P4.4
rent
DC braking time
P4.5
at start
Frequency to
start DC braking
P4.6
during ramp
stop
DC braking time
P4.7
at stop
P4.8
Flux brake
Flux braking
P4.9
current
P4.10
Ramp shape 2
Acceleration
P4.11
time 2
Deceleration
P4.12
time 2
Table 9.5: Motor control parameters
Parameters
Min
Max
Unit
0,0
10,0
s
0,1
3000
s
0,1
3000
s
0.2 x
2 x
A
I
I
Nunit
Nunit
0,00
600.00
s
0,10
10,00
Hz
0,00
600.00
s
0
1
0
7,4
A
0,0
10,0
s
0,1
3000
s
0,1
3000
s
Default
ID
0 = Linear
0,0
500
>0 = S-curve ramp time
1,0
103
1,0
104
Varies
507
0 = DC brake is off at
0
516
start
1,50
515
0 = DC brake is off at
0
508
stop
0 = Off
520
1 = On
519
0 = Linear
0,0
501
>0 = S-curve ramp time
1,0
502
1,0
503
9
47