Motor Settings (Control Panel: Menu Par -> P1) - Honeywell SmartVFD COMPACT User Manual

Variable frequency drives for constant and variable torque applications
Hide thumbs Also See for SmartVFD COMPACT:
Table of Contents

Advertisement

9
44
Code
Parameter
Acceleration
P4.2
time
Deceleration
P4.3
time
AI1 Signal
P6.1
range
AI2 Signal
P6.5
range
(API Full only)
P10.4 Fault autoreset
Parameter
P13.1
conceal
Table 9.1: Quick setup parameters
9.2 MOTOR SETTINGS (CONTROL PANEL: MENU PAR -> P1)
Code
Parameter
Motor nominal
P1.1
voltage
Motor nominal
P1.2
frequency
Motor nominal
P1.3
speed
Motor nominal
P1.4
current
P1.5
Motor cos
P1.7
Current limit
Table 9.2: Motor settings
Parameters
Min
Max
Unit
0,1
3000
0,1
3000
0
3
2
3
0
1
0
1
Min
Max
Unit
180
690
30
320
300
20000
0,2 x
2,0 x
I
I
Nunit
Nunit
0,30
1,00
0,2 x
2 x
I
I
Nunit
Nunit
Default
ID
s
1,0
103
s
1,0
104
0
379
3
390
0
731
1
115
Default
ID
230
V
400
110
600
Hz
50,00
111
rpm
1440
112
I
A
113
Nunit
0,85
120
1,5 x
A
107
I
Nunit
Honeywell
Note
Acceleration time from 0
Hz to maximum fre-
quency
Deceleration time from
maximum frequency to
0 Hz.
API FULL and LIM-
ITED:
0 = Voltage 0...10 V
1 = Voltage 2...10 V
API LIMITED ONLY:
2 = Current 0...20 mA
3 = Current 4...20 mA
NOTE: When using API
LIMITED, select the
voltage/current range
also with the dip switch
2 = Current 0...20 mA
3 = Current 4...20 mA
0 = Not used 1 = Used
0 = All parameters visi-
ble
1 = Only quick setup
parameter group visible
Note
Check rating plate on
the motor
Check rating plate on
the motor
Default applies for a 4-
pole motor.
Check rating plate on
the motor
Check rating plate on
the motor