7.2 CONTROL I/O

Reference
Potentiometer:1~ 10K +/- 5%
Terminal
1
+10Vre Ref. voltage out
2
AI1
3
GND
6
24Vout
7
GND
8
DI1
9
DI2
10 DI3
A A
B B
4
AI2
mA
5
GND
13 GND
14 DI4
15 DI5
16 DI6
18 AO
20 DO
RO 13
22
(NO)
RO 14
23
(NO)
RO 22
24
(NO)
25 RO 21
RO 24
26
(NC)
Table 7.2 : SmartVFD COMPACT General purpose application default I/O
configuration and connections for API FULL version
P) = Programmable function, see parameter lists and descriptions, chapters 9 and 10.
API
API FULL
Signal
Factory preset
Analog signal in 1 Freq. reference
I/O signal ground
24V output for DI's
I/O signal ground
Digital input 1
Start forward
Digital input 2
Start reverse
Digital input 3
Preset speed B0
RS485 signal A
FB Communication Positive
RS485 signal B
FB Communication Negative
Analog signal in 2 PI actual value
I/O signal ground
I/O signal ground
Digital input 4
Preset speed B1
Digital input 5
Fault reset
Digital input 6
Disable PI contr.
Output frequency
Digital signal out
Active = READY
Relay out 1
Active = RUN
Relay out 2
Active = FAULT
Description
Maximum load 10 mA
0 - +10 V Ri = 200 k
P)
(min)
±20 %, max. load 50 mA
P)
0 - +30 V Ri = 12 k
P)
P)
P)
0(4) - 20 mA, Ri = 200
P)
P)
0 - +30V Ri=12 k
P)
P)
0(4) - 20 mA, RL = 500
Open collector, max. load
P)
48V/50mA
Max. switching load:
P)
250Vac/2A or 250Vdc/0.4A
Max. switching load:
P)
250Vac/2A or 250Vdc/0.4A
7
33

min
min