Honeywell SmartVFD COMPACT User Manual page 65

Variable frequency drives for constant and variable torque applications
Hide thumbs Also See for SmartVFD COMPACT:
Table of Contents

Advertisement

64
4.5
D
C BRAKING TIME AT START
DC-brake is activated when the start command is given. This parameter de-
fines the time before the brake is released. After the brake is released, the out-
put frequency increases according to the set start function by par. 2.2.
Figure 10.7: DC braking time at start
4.6
F
REQUENCY TO START DC BRAKING DURING RAMP STOP
The output frequency at which the DC-braking is applied. See Figure 10.9.
4.7
DC
Determines if braking is ON or OFF and the braking time of the DC-brake
when the motor is stopping. The function of the DC-brake depends on the stop
function, par. 2.3.
Par. 2.3 = 0 (Stop function = Coasting):
After the stop command, the motor coasts to a stop without control from the
frequency converter.
With the DC injection, the motor can be electrically stopped in the shortest
possible time, without using an optional external braking resistor.
The braking time is scaled by the frequency when the DC-braking starts. If the
frequency is greater, or equal to the nominal frequency of the motor, the set
value of parameter 4.7 determines the braking time. For example, when the
frequency is 10% of the nominal, the braking time is 10% of the set value of
parameter 4.7.
10
Parameter Descriptions
Output
frequency
Par 4.5
RUN
STOP
BRAKING TIME AT STOP
0 = DC brake is not in use
>0 = DC brake is in use and its function depends on the Stop function,
(par. 2.3). The DC braking time is determined with this parameter.
Honeywell
t

Hide quick links:

Advertisement