Propylene Glycol Flow

The table below summarizes the flow for the P-K SONIC appliances with different Propylene Glycol
mixtures:
Model 
SC-1500
Mixture 
Flow
0%
145 GPM
10%
147 GPM
20%
148 GPM
30%
151 GPM
40%
157 GPM
50%
164 GPM
60%
172 GPM
Revised: June 2, 2017
Released: June 2, 2017
SC-2000
Pressure Flow
20.5 ft
192 GPM
21 ft
194 GPM
21.5 ft
197 GPM
22 ft
200 GPM
24 ft
208 GPM
26 ft
217 GPM
29 ft
228 GPM
 HARSCO Industrial, Patterson-Kelley 2017
All Rights Reserved.
Technical Service 1.877.728.5351
SC-3000
Pressure Flow
35 ft
285 GPM
37 ft
294 GPM
38 ft
298 GPM
39 ft
303 GPM
42 ft
314 GPM
46 ft
329 GPM
51 ft
345 GPM
1004905978 P-K SONIC NURO Installation and
®
P-K SONIC
Gas Fired Boiler
SC-4000
Pressure Flow
17.5 ft
384 GPM
18.5 ft
389 GPM
19 ft
394 GPM
20 ft
400 GPM
21 ft
415 GPM
23 ft
434 GPM
26 ft
456 GPM
Owners Manual (Rev F Jun-2017).docx
Page 105
Pressure
32 ft
32.5 ft
33 ft
34.5 ft
37 ft
40.5 ft
45 ft

Advertisement