assignments are very specific. They are also different from each other, as illustrated in the
HUB10.3 literature.
Master Power Save Level appears on an inverter which is set as master (the default setting). The range
of rank numbers is 0 to 10. The default value is 0. The master is normally left at this value.
The Master Power Save Level function is used for the master inverter on Port 1. It is also used for
any subphase masters in a series or three-phase system. The ranking of a subphase master is
treated the same as the master. If the master is set at 0, subphase masters should also be 0.
Slave Power Save Level appears on an inverter which is set as slave. The range of rank numbers is 1
to 10. (The default value for all ports is 1.)
When subphase master inverters are in use, the slaves for the additional phases are ranked
identically to the slaves on the master phase. If the master inverter has two slaves ranked 1 and 2,
any other phases should also rank their slaves 1 and 2. Slaves on multiple phases should not be
ranked sequentially (1 through 6 and so on). This would cause delays in output.
The ranks are prioritized so that lower-numbered ranks turn on sooner and higher ranks turn on
later. The lowest-ranked inverter does not go silent and remains on unless ordered otherwise.
The lowest-ranked inverter is expected to be the master. The priorities are the same across both
screens. If Port 1 (master) is set at 0 and Port 2 (slave) is set at 1, the slave will turn on later.
Since the Master item is the only one that goes to 0, it is easy to ensure that all slave inverters
go silent. (To force all slaves to be active, simply set the master at a higher rank than the slaves.)
Subphase master inverters are set at 0 because all phases must have at least one inverter that
does not enter Silent mode. The slaves for each phase are set identically to each other so that all
phases receive additional power at the same time as needed.
IMPORTANT:
Set the master (or subphase) rank at 0 and arrange the slave ranks in order (1, 2, 3, 4, etc.). Another
order may defeat the purpose of Power Save mode. Leaving the master at 0 makes power available
from the master; the other inverters should not be active. If a slave is ranked lower (prioritized
higher) than the master, that slave will not go silent.
NOTE : Disregard this rule if the installation requires some slaves to be continuously active.
IMPORTANT:
Do not give slave inverters the same rank numbers. If, for example, multiple slaves were all ranked
at 1, they would all come on at the same time. Once they came on, the divided load would cause the
master to detect a minimal load on its output, so it would shut off all the slaves, at which point the
master would read a high load again. This could quickly escalate into a rapid on/off cycling of
inverters and could cause long-term system problems.
NOTE :
Power Save is used by the battery chargers of stacked systems with slave inverters. Not every
charger is activated at once. Initially the master inverter is the only active charger. The batteries will
absorb current up to the maximum for all chargers. When the batteries (and the master) draw more
than 12 Aac, the master will turn on the first slave charger. The batteries will absorb that additional
current and more. The master will then turn on more slaves until all active chargers are operating.
If the master Charger AC Limit is turned to 11 or less, it will not turn on any slaves and will remain
the only charger. For more information on charging with stacked inverters, see the FXR Series
Inverter/Charger Operator's Manual.
Figure 33 shows a system of four FXR2012A inverters (the master and three slaves). These
inverters in a parallel system with a common load bus.
The captions at the top indicate the ranking of each inverter.
The captions also show the port assignments on the communications manager (1 through 4).
The notations at the bottom show how the inverter are activated in sequence as loads of 12 Aac
are applied.