Ac And Dc Cable Requirements - M88H_122 (Cf); Ac Cable - Delta M88H_121 (ST) Quick Installation Manual

Solar power inverter; st product version j; cf product version d
Table of Contents

Advertisement

AC and DC cable requirements – M88H_122 (CF)

AC cable

General information on AC terminal block
The section describes the general technical characteristics of
the AC terminal blocks. The special features which apply to the
installation of the inverter are explained in the following sections.
The specifications in this section have been
defined by Phoenix Contact. Check if the techni-
cal specifications have change before starting
installation work, see www.phoenixcontact.com.
ATTENTION
Danger of a cable fire.
Bending and twisting causes damage to the
inner structure of the conductor, which leads to
punctiform increase in electrical resistance. This
can result in an overheating of the conductor
and destruction of the insulation.
► When bending and twisting cables or
conductors, always comply with the
manufacturer's instructions.
AC terminal block specifications
Designation
Connection type
Screw thread
Rated current I
N
Rated voltage U
N
Attaching the conductor
Type of attachment
Tightening torque
Specification for copper cable
Min./max. Wire cross-section
Without wire end sleeve
rigid cable
flexible cable
with wire end sleeve
Flexible cable (wire end sleeve
without plastic sleeve)
flexible cable (wire end sleeve with
plastic sleeve)
Stripping length
20
Phoenix Contact UKH 70
Screws with hexagon socket head
M8
96 A
1000 V
M8 screws with hexagon socket
head
8 ... 10 Nm
16 ... 95 mm
2
25 ... 70 mm
2
16 ... 70 mm
2
16 ... 70 mm
2
24 mm
Specification for aluminum cable
SE
RE
The most important cable types for aluminum cable
SE
sector-shaped, solid conductor
SM-S
sector-shaped, multi-conductor, rigid wires
SM-L
sector-shaped, multi-conductor, (stranded wires)
RE
round, solid conductor
RM-S
round, multi-conductor, rigid wires
RM-L
round, multi-conductor, (stranded wires)
The terminals have been specially developed for direct connec-
tion of sector-shaped solid conductor (SE) aluminum cables:
Min./max. Conductor cross-section
Stripping length
SE
Quick Installation Guide for Solar Power Inverter M88H EU V3 EN 5013240202 02 2018-03-22
SM-S
SM-L
RM-S
RM-L
50 / 70 mm
2
24 mm
90°