Honeywell JADE W7220 Installation Instructions Manual page 15

Economizer module
Hide thumbs Also See for JADE W7220:
Table of Contents

Advertisement

Menu
Parameter
SETPOINTS
ERV OAT SP
CONTINUED
EXH1 SET
EXH2 SET
SYSTEM
INSTALL
SETUP
UNITS DEG
EQUIPMENT
AUX2 IN
FAN SPEED
FAN CFM
AUX1 OUT
OCC
Table 4. Menu Structure
Parameter
Default
Value
32ºF
0 to 50 ºF;
d
increment by 1
50%
0 to 100%;
increment by 1
75%
0 to 100%;
increment by 1
01/01/11
ºF
ºF or ºC
CONV
CONV
HP
n/a
Shutdown (SD)
Heat (W1)
HP(O)
HP(B)
1 speed
1 speed/
2 speed
5000cfm
100 to 50000
cfm;
increment by
100
NONE
NONE
ERV
EXH2
SYS
INPUT
INPUT or
ALWAYS
a
. (Continued)
Parameter
Range and
b
Increment
Only when AUX1 O = ERV
Setpoint for OA damper position when exhaust fan 1 is powered
by the economizer.
With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and
Exh1 H is 50%
Setpoint for OA damper position when exhaust fan 2 is powered
by the economizer. Only used when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high
speed fan) settings are required. Default for Exh2 L is 80% and
Exh2 H is 75%
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
Sets economizer controller in degrees Fahrenheit or Celsius.
CONV = conventional.
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller (O or B terminal).
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must pro-
gram CONV mode for W. Shutdown is not
available in the two-speed fan mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
Sets economizer controller for operation of 1 speed or 2 speed
supply fan. The controller does not control the fan but positions
the OA and RA dampers to the heating or cooling mode settings.
NOTE: 2-speed fan option also needs Heat (W1) pro-
grammed in AUX 2 In.
This is the capacity of the fan. The value is found on the label
from the RTU manufacturer. The cfm of the fan is only used with
DCV CAL ENABLE AUO
• NONE = not configured (output is not used)
• ERV= Energy Recovery Ventilator
• EXH2 = second damper position 24 Vac out for second
exhaust fan.
• SYS = use output as an alarm signal
When using a setback thermostat with occupancy out (24 Vac),
the 24 Vac is input "INPUT" to the OCC terminal. If no
occupancy output from the thermostat then change program to
"ALWAYS" OR add a jumper from terminal R to OCC terminal.
15
JADE
ECONOMIZER MODULE
Notes
d
62-0331—13