Damper Minimum Position Settings And Readings On Checkout Menu - Honeywell JADE W7220 Installation Instructions Manual

Economizer module
Hide thumbs Also See for JADE W7220:
Table of Contents

Advertisement

JADE
ECONOMIZER MODULE
Menu
Parameter
ALARMS(#)
SYS ALARM
CONTINUED
ACT UNDER V
ACT OVER V
ACT STALLED
FEATURES ADJUSTABLE ONLY BY USE OF THE W7220 PC MOD TOOL
ACT STALL ALARM
SUPPRESSION
a
Table 4 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
b
When values are displayed, pressing and holding the
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In
the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
e
When used with Honeywell communicating actuator the damper out is reported in XX.X% open versus XX.X Vdc.
f
After 10 minutes without a command or mode change, the controller will change to normal operation.
Table 5. Damper minimum position settings and readings on checkout menu.
Fan Speed
1
1
2
2
1
1
2
2
2
2
62-0331—13
Table 4. Menu Structure
Parameter
Parameter
Range and
Default
Value
Increment
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Disabled
Enabled or
Disabled
) sensor, then none of the DCV parameters appear.
2
or
button causes the display to automatically increment.
Demand Control Ventilation
(CO2 Sensor)
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
18
a
. (Continued)
b
When AUX1-O is set to SYS and there is any alarm (e.g., failed
sensors, etc.), the AUX1-O terminal has 24 Vac out.
Voltage received by Actuator is below expected range
Voltage received by Actuator is above expected range
Actuator stopped before achieving commanded position
If enabled this feature allows the operator to suppress the stall
alarm in a specific range of the actuator stroke.
Setpoints
Checkout
MIN POS
VMAX-HS
N/A
N/A
MIN POS H
VMAX-HS
MIN POS L
VMAX-LS
VENT MIN
VMIN-HS
VENT MAX
VMAX-HS
VENT MIN H
VMIN-HS
VENT MAX H
VMAX-LS
VENT MINL
N/A
VENT MAX L
N/A
Notes