SEQUENCE OF OPERATION

OA Good to
DCV
economize?
None
No
None
Yes
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
the call for Y1-I and Y2-I have not been satisfied.
OA Good to
DCV
economize?
Below CO2
No
set
Yes
Above CO2
No
set
Yes
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
the call for Y1-I and Y2-I have not been satisfied.
Table 6. Dry Bulb Operation No DCV (CO2 sensor) - 1 Speed Fan.
Y1-I
Y2-I
FAN SPD
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Table 7. Dry Bulb Operation With DCV (CO2 sensor) - 1 Speed Fan.
Y1-I
Y2-I
FAN SPD
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Y1-O
Y2-O
0-v/Off
0-v/Off
MIN POS
24-v/On
0-v/Off
MIN POS
24-v/On
24-v/On
MIN POS
0-v/Off
0-v/Off
MIN POS
0-v/Off
0-v/Off
MIN POS to Full-
Open
24-v/On
MIN POS to Full-
a
0-v/Off
Open
Y1-O
Y2-O
0-v/Off
0-v/Off
VENTMIN
24-v/On
0-v/Off
VENTMIN
24-v/On
24-v/On
VENTMIN
0-v/Off
0-v/Off
VENTMIN
0-v/Off
0-v/Off
VENTMIN to Full-
Open
24-v/On
VENTMIN to Full-
a
0-v/Off
Open
0-v/Off
0-v/Off
VENTMIN to
VENTMAX
24-v/On
0-v/Off
VENTMIN to
VENTMAX
24-v/On
24-v/On
VENTMIN to
VENTMAX
0-v/Off
0-v/Off
VENTMIN to
VENTMAX
0-v/Off
0-v/Off
VENTMIN to Full-
Open
24-v/On
VENTMIN to Full-
a
0-v/Off
Open
19
JADE
ECONOMIZER MODULE
Occupied
Unoccupied
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
Occupied
Unoccupied
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
62-0331—13