2-Position Actuator; Single Enthalpy Curves And Boundaries; Single Enthalpy And Dual Enthalpy High Limit Curves - Honeywell JADE W7220 Installation Instructions Manual

Economizer module
Hide thumbs Also See for JADE W7220:
Table of Contents

Advertisement

ECONOMIZING
AVAILABLE
NOT AVAILABLE
TEMPERATURE
Enthalpy
Temp.
Curve
Dry-Bulb (°F)
ES1
80.0
ES2
75.0
ES3
70.0
ES4
65.0
ES5
60.0
HL
86.0
EXH1 OR AUX1 O
C
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1
O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN
PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT
OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE
EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS
DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL
PROGRAM AUX1 O FOR EXH2.
Fig. 9. 2-position actuator.
Fig. 10. Single Enthalpy curves and boundaries.
Table 3. Single Enthalpy and Dual Enthalpy High Limit Curves.
Temp.
Enthalpy
Dewpoint (°F)
(btu/lb/da)
60.0
28.0
57.0
26.0
54.0
24.0
51.0
22.0
48.0
20.0
66.0
32.4
1
V
2
ACTUATOR
M33409
Point P1
Temp. °F
Humidity %RH
80.0
36.8
75.0
39.6
70.0
42.3
65.0
44.8
60.0
46.9
86.0
38.9
11
JADE
ECONOMIZER MODULE
DUAL ENTHALPY
HIGH LIMIT
SINGLE ENTHALPY
P2 (T,RH)
P1
(T,RH)
ES5
ES4
ES3
ES2
ES1
Point P2
Temp. °F
Humidity %RH
66.3
63.3
59.7
55.7
51.3
72.4
HL
M32286
80.1
80.0
81.4
84.2
88.5
80.3
62-0331—13