Honeywell JADE W7220 Installation Instructions Manual page 17

Economizer module
Hide thumbs Also See for JADE W7220:
Table of Contents

Advertisement

Menu
Parameter
DAMPER MINIMUM
f
CHECKOUT
POSITION
DAMPER OPEN
DAMPER CLOSE
CONNECT Y1-O
CONNECT Y2-O
CONNECT AUX1-O
CONNECT EXH1
ALARMS(#)
MA T SENS ERR
CO2 SENS ERR
OA SYLK T ERR
OA SYLK H ERR
RA SYLK T ERR
RA SYLK H ERR
DA SYLK T ERR
OA SENS T ERR
ACT ERROR
FREEZE ALARM
SHUTDOWN ACTIVE
DMP CAL RUNNING
DA SENS ALM
Table 4. Menu Structure
Parameter
Parameter
Range and
Default
b
Value
Increment
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
17
JADE
a
. (Continued)
The checkout for the damper minimum positions is based on the
system. See Table 5.
Positions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test.
Make sure you pause in this mode to allow for exhaust contacts
to energize due to the delay in the system.
Positions damper to the fully closed position.
Closes the Y1-O relay (Y1-O).
See CAUTION on page 23
Closes the Y2-O relay (Y2-O).
See CAUTION on page 23
Energizes the AUX1-O output.
Closes the power exhaust fan 1 relay (EXH1)
Alarms display only when they are active. The menu title
"ALARMS (#)" includes the number of active alarms in
parenthesis (). When using SYLK bus sensors, "SYLK" will
appear on the screen, and when using 20k OA temperature
sensors, "SENS T" will appear on the screen.
Mixed air sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues
CO2 sensor has failed, gone out of range or become
disconnected - check wiring then replace sensor if the alarm
continues
Outdoor air enthalpy sensor has failed or become disconnected -
check wiring then replace sensor if the alarm continues
Return air enthalpy sensor has failed or become disconnected -
check wiring then replace sensor if the alarm continues
Discharge air sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues
Outdoor air temperature sensor has failed or become
disconnected - check wiring then replace sensor if the alarm
continues
Actuator has failed or become disconnected - check for stall,
over voltage, under voltage and actuator count. Replace actuator
if damper is moveable and supply voltage is between 21.6 V and
26.4 V. Check actuator count on STATUS menu.
Check if outdoor temperature is below the LOW Temp Lockout
on setpoint menu. Check if Mixed air temperature on STATUS
menu is below the Lo Setpoint on Advanced setup menu. When
conditions are back in normal range then the alarm will go away.
AUX2 IN is programmed for SHUTDOWN and 24 V has been
applied to AUX2 IN terminal
If DCV Auto enable has been programmed, when the JADE is
completing a calibration on the dampers, this alarm will display.
Wait until the calibration is completed and the alarm will go
away. Must have OA, MA and RA sensors for DCV calibration;
set up is in the Advanced setup menu
Discharge air temperature is out of the range set in the
ADVANCED SETUP Menu. Check the temperature of the
discharge air.
ECONOMIZER MODULE
Notes
62-0331—13