Wiring
2-3-2

Connector Wiring Methods

!Caution
Terminal Block Unit
22
Be sure that all the connectors are wired correctly and properly connected to the
Counter Unit, to prevent the Unit from malfunctioning.
To wire the CJ1W-CTL41-E in order to connect the external signals three methods
are available:
1. Directly connecting the wires and cables to an external connector. Recom-
mended connectors are 40-pin MIL-C-83503 (or DIN 41651 or IEC 60603-1)
compatible 40-pole connectors.
2. Indirectly connecting the wires and cables to the screw terminals of an XW2B-
40Gx Terminal Block Unit, which is connected to the Unit with a standard
XW2Z I/O cable. Both parts can be ordered separately.
3. Indirectly connecting the wires and cables to the screw-less terminals of an
XW2G-40G7-E Terminal Block Unit, which is connected to the Unit with a
standard XW2Z I/O cable. Both parts can be ordered separately.
The figures below show the XW2B-40Gx and XW2G-40G7-E Input Terminal
Blocks.
The following Terminal Block Units are recommended for using together with the
CJ1W-CTL41-E Counter Unit:
Item
Description
XW2B-40G4
40 screw terminals (M2.4)
XW2B-40G5
40 screw terminals (M3.5)
XW2D-40G6
40 screw terminals, compact
XW2G-40G7-E
36 screwless terminals
Section 2-3
Input type supported
Line driver only
Line driver only
Line driver only
Line driver / 24 Vdc