Reference operating
conditions
Long-term stability
Maximum measured error
of analog output
(under reference operating
conditions)
Switch point
Rise time (T90)
Settling time
1)
extended specifications apply to customer-specific measuring ranges
8
Performance characteristics
as per DIN IEC 60770, T
= 25 °C
U
≤ 0.15 % of URL per year
The measured error comprises the non-linearity including hysteresis and non-reproducibility in accordance
with the limit point method as per IEC 60770.
PMC131
• ≤ 0.5 % of (URL - LRL) x TD
Example: PMC131 version "A1R"
• Nominal value = 10 bar
• Upper range value (URV) = 6 bar
• Lower range value (LRV) = 0 bar
Turn down (is set at factory):
• Nominal value / (URV – LRV)⏐= 10 bar/6 bar = 10:6
PMP131 and PMP135
• ≤ 0.5 % of URL
PMP131 and PMP135
• Deviation: ≤ 1 % of URL
• Non-reproducibility: ≤ 0.5 % of URL
PMC131
20 ms
PMP131 and PMP135
2 to 5 ms
1)
LRL = LRV
0 bar
Example: PMC131 version "A1R"
set span: 0 to 6 bar; nominal value = 10 bar
1
2
3
LRL
URL
LRV
URV
1
URV
+6 bar
3
Span set and calibrated at the factory (measuring
range)
Nominal value i Upper Range Limit (URL)
Sensor measuring range
Lower Range Limit
Upper Range Limit
Lower Range Value
Upper Range Value
Endress+Hauser
Cerabar T
URL
+10 bar
2
P01-PMx13xxx-05-xx-xx-xx-001