Confirming The I/O Allocation And Slot Number; Confirming The I/O Number Allocations - Panasonic FP2 User Manual

Serial data unit
Hide thumbs Also See for FP2:
Table of Contents

Advertisement

FP2 Serial Data Unit
3.3.3

Confirming the I/O Allocation and Slot Number

The I/O numbers and slot numbers are always necessary when creating a program.
These vary depending on the position at which the serial data unit is installed in the
backplane. Always check to see if the numbers match the design.
3.3.3.1

Confirming the I/O Number Allocations

The occupied I/O areas for all of the units mounted between the CPU unit and the FP2
serial data unit should be confirmed. These are allocated as I/O areas for the serial data
unit, starting from the serial number.
Example:
The following is an example of FP2 serial data unit being
mounted in succession following three 16−point I/O units.
FP2 CPU unit
Notes
If there are any empty slots between the CPU unit and the
serial data unit, check to see whether an I/O area has been
allocated to the empty slot.
If I/O mount allocation and automatic allocation are being
carried out, 16 points for each type of allocation will
automatically be assigned to empty slots.
If the CPU unit being used is a 2−module type, also check any
I/O areas occupying the units incorporated in the CPU unit.
For information on how I/O allocations are made, refer to the
FP2/FP2SH User's Manual.
0
1
Slot No.
X0
Y10
to
to
XF
Y1F
(WX0)
(WY1)
Confirming the Unit Settings and Design Contents
3.3 Confirming the I/O Contacts and Slot Number
FP2 serial data unit
2
3
4
SDU
SD RD ERR SD RD ERR AL
COM.1
COM.2
COM.1(RS232C)
COM.2(RS232C)
Y20
X30 to X2F (WX3) Y40 to Y4F (WY4)
to
Y2F
(WY2)
3 − 11