9. ANNExES.

9.1. general TeChniCal speCifiCaTions.

Models.
Available power ratings (VA / W).
Technology.
Input.
Input type.
number of cables.
Rated voltage.
Input voltage range.
Input frequency range.
Inverter.
waveform.
Power factor.
Rated voltage.
output voltage accuracy (battery mode).
Total harmonic distortion (Thdv), with linear load.
frequency.
Transfer time, line mode to battery mode (normal mode).
Compatibility with APfC loads.
Performance at full load, in normal mode
with battery 100% charged.
Performance at full load, in battery mode.
overload in line mode
overload in battery mode.
Batteries (AGM sealed 3 - 5 years life).
element voltage.
Capacity.
number of batteries in device connected in series / group voltage.
Low battery voltage.
blocking voltage for group end of backup.
Internal battery charger.
group floating voltage.
maximum charge current.
Recharge time.
Other functions.
Cold start.
emergency power off (ePo).
General.
IeC input connectors.
IeC output connectors.
Communication ports.
Connector for external ePo installation
Slot for optional cards.
monitoring software.
Audible noise at 1 m in battery mode.
operating temperature.
Storage temperature with batteries.
Storage temperature without batteries.
working altitude.
Relative humidity.
Protection rating.
dimensions (mm) depth x width x height.
weight (kg).
Safety.
electromagnetic compatibility (emC).
24
ADVANCE R
750VA / 450W
1000VA / 600W
Line-interactive with sine-wave output.
Single-phase.
3 cables - Phase R (L) + neutral (n) and earth.
220 / 230 / 240 v AC
165..290 v AC
50 / 60 hz (auto-detectable).
Pure sine wave.
220 / 230 / 240 v AC
< 5 % linear load
<10 % non-linear load
50 / 60 hz.
with mains absent -backup mode- 50 / 60 ±1% hz.
> 95 %
> 78 %
> 110 % ±10 % Audible alarm and fault after 1 min
> 120 % ±10 % Immediate fault
> 110 % ±10 % Audible alarm and fault after 1 min
> 120 % ±10 % Immediate fault
6 v dC
9 Ah
2 / 12 v dC
11.7 v
10.5 v
13.65 v
4 hours to 90%
IeC 60320 C14 10A
IeC 60320 C13
(RS232 - db9).
SnmP
Powermaster (free download).
< 40 db
0..+40ºC
–20..+50 ºC
–20..+70 ºC
2,400 masl (power degradation up to 5,000 m)
0..90 % non-condensing.
216x433x44 (1 U)
8.6
en IeC 60950-1
en IeC 60240-1
en IeC 60240-2
1500VA / 900W
0.6
±10%
4 ms
yes
> 80 %
7 Ah
9 Ah
4 / 24 v dC
22.2 v
20.5 v
27.5 v
1 A
yes
yes
yes
IP20
485x433x44 (1 U)
14.2
16.2
SALICRU