Salicru SPS.ADVANCE RT series User Manual

Salicru SPS.ADVANCE RT series User Manual

Sps.advance rt series
Table of Contents

Advertisement

UNINTERRUPTIBLE POWER SUPPLY (UPS) + LIGHTING FLOW DIMMER STABILIZERS (ILUEST) + SWITCH MODE POWER SUPPLY + STATIC INVERTERS + PHOTOVOLTAIC INVERTERS + VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS
UNINTERRUPTIBLE POWER SUPPLY
SPS.ADVANCE RT series
USER'S MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Salicru SPS.ADVANCE RT series

  • Page 1 UNINTERRUPTIBLE POWER SUPPLY (UPS) + LIGHTING FLOW DIMMER STABILIZERS (ILUEST) + SWITCH MODE POWER SUPPLY + STATIC INVERTERS + PHOTOVOLTAIC INVERTERS + VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS UNINTERRUPTIBLE POWER SUPPLY SPS.ADVANCE RT series USER'S MANUAL...
  • Page 3: Table Of Contents

    4.3.6. Communication port. 4.3.6.1. RS232 and USB interface. 4.3.6.2. Smart slot. 4.3.6.3. AS400 Interface with DB9 output (option). 4.3.6.4. Protection against transient voltages for modem / ADSL / Fax / ... lines. 4.3.7. Software. 4.3.8. Considerations before commissioning with load connected. SALICRU...
  • Page 4: Introduction

    «Main protective earthing terminal» symbol. Connect the earth cable coming from the installation to this terminal. Yours sincerely. SALICRU «Earth bonding terminal». Connect the earth cable coming from the load and the external battery cabinet to this terminal. ˆ The equipment here described can cause important physical damages due to wrong handling.
  • Page 5: General Safety Warnings

    «Off» (deactivated) it doesn't mean that at the output there will not be voltage. All outlets of the UPS has an earth bonding, duly connected SALICRU...
  • Page 6: To Keep In Mind

    So, to do it, the input and static bypass switches will have to • Do not store, install or expose the equipment in corrosive, be turned «Off». wets, dusty inflammable or explosive environments and never outdoors. Put warnings of danger and/or emergency switches if the safety Standards require it in your particular installation.
  • Page 7 • Never short the battery terminals as it involves a high risk. It involves the detriment of the equipment and batteries. • Avoid mechanical efforts and impacts. • Do not open or mutilate the battery. Spilled electrolyte is harmful and toxic to the skin and eyes. SALICRU...
  • Page 8: Quality And Standard Guarantee

    Quality and standard 2.3. Environment. guarantee. This product has been designed to respect the environment and has been manufactured in accordance with the standard ISO 14001. 2.1. Declaration of the management. Equipment recycling at the end of its useful life: Our company commits to use the services of authorised socie- Our target is the client’s satisfaction, therefore this Management ties and according to the regulations, in order to treat the recov-...
  • Page 9: Presentation

    Plastic beauty front Plastic beauty front Front virew ADVANCE RT Fixing screws, Plastic beauty front Front view battery module for ADVANCE RT Fig. 1. Front view models from 0,7 to 10 kVA and battery modules for extended back up times. SALICRU...
  • Page 10 Output connector, with Módem USB COM / ADSL / Fax / ... protection port Standard 750 and IEC inlet for AC 1000 VA models power supply IEC outlets RS232 COM Earth connection Input connector, for modem / ADSL / Fax / ... line port for battery module IEC outlets...
  • Page 11: Definition Of The Product

    (B1) Equipment with extra battery charger. The equip- ment is supplied without batteries and without ac- SALICRU...
  • Page 12: Description And Operating Principle

    3.3. Description and operating 3.3.1. Main features. principle. • Control by microprocessor with high reliability. • Design of high frequency. This user's manual describes the installation and operating of • Stabilizer with «Boost» and «Buck» technology. the Uninterruptible Power Supply (UPS) from SPS.ADVANCE • Selectable output range and line sensitivity.
  • Page 13: Isolation Transformer

    The isolation transformer can be installed at the input or output of the UPS from SPS.ADVANCE RT series and it will always be located out from the equipment enclosure. 3.4.2. External maintenance manual bypass.
  • Page 14: Installation

    Installation. because due to its specification of isolation it will prevent the triggering of the protections fitted in the primary of the trans- former in case of electrical shock in the secondary (output of the isolation transformer). • Check the Safety instructions, from section 1.2.3. • Remind you that all external isolation transformers already installed or supplied from factory, has the neutral of the sec- • Check that the data in the nameplate are the required by the...
  • Page 15: Storage

    4.2.4. Vertical assembling -tower type- or rack. • All the UPSs from SPS.ADVANCE RT series are designed to assemble the equipment as tower format -vertical position of the equipment- or rack -horizontal position- for its installa- tion in 19"...
  • Page 16: Rotation Of Control Panel With Lcd Panel

    • To take out the beautiful front cover, proceed as follows (see figure 4): ˆ Remove the two fixing screws "C" from beautiful plastic front cover. ˆ Move the front cover to "D" direction, by applying a hard and moderated knock on its side (side without screws), to free the trim entered into the metallic frame.
  • Page 17: Rack Cabinet Assembling

    ˆ Put a UPS in a rack cabinet, it is needed to have the side internal rail as support mode "C". In lack of them and under request, a rails can be supplied as a guide, to be SALICRU...
  • Page 18: Rack Cabinet Assembling, With Extended Back Up Time (Battery

    installed by the end user. Make the assembling at the required height, assuring the correct torque of the fixing screws. ˆ Face the equipment over the rails and enter it to the bottom. Depending on the model of the equipment and as a result of the weight, it is recommended to make the installation works by two persons, and even more when they are done on the top and bottom of the cabinet.
  • Page 19: Connection Of Input

    Anderson connector. This schuko plug to the AC mains outlet. connector is not available in models up to 1kVA. • For battery connection with the equipment, follow the stated steps in sections 4.2.4.4 and 4.2.4.6, keeping in mind the model. SALICRU...
  • Page 20: Epo Terminals In Upss > 1Kva (Emergency Power Off

    • Through the control panel, it can be selected the reverse • Each battery module is independent for each equip- functionality, normally closed (NC). ment. It is completely forbidden to connect to equip- ments to the same battery module. Less punctual cases, it is not recommended to use this type of connection due to the function of the EPO button, because it would not work in case of any of the two cables that goes Minimum features of fast...
  • Page 21: As400 Interface With Db9 Output (Option

    Fig. 10. AS400 dry contact pin-out. • Installation procedure: ˆ Go to website: Description Pin-out Input/output http://support.salicru.com UPS fault Output ˆ Choose the operating platform that you need and follow General alarm Output the instructions described in the web site to download the software.
  • Page 22 Nevertheless, when it is done, it will be done gradually to avoid any problem, as minimum in the first commissioning. • If inductive loads with big inrush current apart from sensi- tive ones are required to be connected like laser printers or CRT monitors, keep in mind the start inrush currents of these peripherals in order to avoid that the equipment becomes blocked under the worst conditions.
  • Page 23: Operating

    • Fan will be started up and the LCD from control panel will show the status of the equipment. • After several seconds, the UPS is established on "NORM" (Line mode). If the mains voltage is wrong, the UPS will shift SALICRU...
  • Page 24: Control Panel

    Control panel. • The following critical alarms do not allow deactivating the own acoustic alarm: Low battery, Fan fault, internal Over temperature in the equip- ment and battery fault or damaged. • The acoustic alarm can be deactivated when beeping, 6.1.
  • Page 25: Graphics Displayed In The Lcd Panel

    • To set the IEC outlet group through the LCD panel of the equipment, proceed as follows: ˆ 1.- Enter into the configuration mode. Press the key for more than 3 seconds and the UPS will shift to setting mode. SALICRU...
  • Page 26: Setting The Ups To Connect It With "N" Battery Modules

    ˆ 2.- Select the configuration elements. ˆ 3.- Validate the configuration element. Press the key to select the configurable elements When the LCD panel displays "GF", press the key stated in table 10 and go forward or backward till reaching more than one second to enter into the element to set.
  • Page 27: Maintenance, Warranty And Service

    1.2.3.3 side. • The equipment from SPS.ADVANCE RT series only requires Therefore, before doing any reparation or maintenance task, a minimum maintenance. The used battery in the standard the internal battery fuses and/or the interlink connections be- models is lead acid, sealed, VRLA and maintenance free.
  • Page 28: Faq. General Indications

    7.2.2. FAQ. General indications. Problem Possible cause Solution The equipment doesn't start up when pressing Internal fuse blown. Consult with the S.T.S.. over the corresponding key. Jumpers at the output are not connected Connect the output jumpers. The equipment is ON but the loads do not properly.
  • Page 29: Technical Service Network

    Consult our Website to have more information 7.5. Technical service network. Coverage, both national and international, from our Service and Technical Support (S.T.S.), can be found in our Website. SALICRU...
  • Page 30: Annexes

    Annexes. 8.1. Main general specifications. Models: SPS.ADV RT Available powers (kVA / kW) 0.750 / 0.675 1 / 0.9 1.5 / 1.35 1.5 / 1.35 (B1) 2 / 1.8 2 / 1.8 (B1) 3 / 2.7 3 / 2.7 (B1) Technology Line interactive with sinewave output Input...
  • Page 31: Glossary

    (real time) samples are received, usually coming from an power but in alternating current can defer depending on the analogical/digital converter(ADC). power factor. • Power factor.- It is defined as power factor, p.f., of an alter- nating current circuit, as the ratio between the active power, SALICRU...
  • Page 32 • LCD.- LCD acronym of Liquid Crystal Display, device in- vented by Jack Janning, who was employee of NCR. It is an electric system of data presentation based on 2 transparent conductor layers and in the middle a special crystal liquid that have the capacity to orientate the light when trespassing.
  • Page 33 SALICRU...
  • Page 34  : ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ USER MANUAL...
  • Page 35  : ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ SALICRU...
  • Page 36 BARCELONA Tel. +34 93 848 24 00 902 48 24 00 (Only Spain) Fax. +34 94 848 11 51 salicru@salicru.com Tel. (S.T.S.) +34 93 848 24 00 902 48 24 01 (Only Spain) Fax. (S.T.S.) +34 93 848 22 05 sst@salicru.com...