Mitsubishi Electric FR-D720S-008SC Original Instruction page 34

Fr-d700 sc series installation guideline fr-d720s-008sc to 100sc-ec fr-d740-012sc to 160sc-ec
Table of Contents

Advertisement

APPENDIX
Environment
Ambient temperature
Ambient humidity
Maximum altitude
Wiring protection
Select a UL and cUL certified fuse with Class T fuse equivalent cut-off speed or faster with the appropriate rating for branch circuit
protection, or a UL489 molded case circuit breaker (MCCB) in accordance with the tables below.
FR-D720S-
SC-EC (C)
Rated fuse voltage [V]
Without power factor
improving reactor
Fuse maximum
allowable rating [A] *
With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating [A] *
FR-D740-
SC-EC (C)
Rated fuse voltage [V]
Without power factor
improving reactor
Fuse maximum
allowable rating [A] *
With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating [A] *
* Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
Motor Overload Protection
The frequency inverters FR-D700 SC are equipped with a UL certified internal electronic thermal relay function.
When using the electronic thermal relay as motor overload protection, set the rated motor current to Pr. 9 Electronic thermal O/L relay.
Electronic thermal relay function operation characteristic
Pr. 9 = 50 % setting of
*1, 2
inverter rating
*3
or more
Inverter output current (%)
(% to the rated inverter current)
28
During Operation
–10 °C to +50 °C
90 % RH or less
(non condensing)
1000 m
008
15
15
15
012
022
6
10
6
10
15
15
Pr. 9 = 100 % setting of
*2
inverter rating
*3
or more
Operation region
Region on the right of
characteristic curve
Non-operation region
Region on the left of
characteristic curve
Characteristic when electronic
thermal relay function for motor
protection is turned OFF
(Pr. 9 = 0 (A))
Region for
transistor
protection
In Storage
–20 °C to +65 °C
90 % RH or less
(non condensing)
1000 m
014
025
240 V or more
20
20
20
20
15
15
036
050
480 V or more
15
20
10
15
15
15
This function detects the overload (overheat) of the motor,
stops the operation of the inverter's output transistor, and
stops the output.
When using the Mitsubishi Electric constant-torque motor
set "1" or any of "13", "50" or "53" in Pr. 71. This provides
a 100 % continuous torque characteristic in the low-speed
range. Set the rated current of the motor in Pr. 9.
*1
When 50 % of the inverter rated output current (current value)
is set in Pr. 9.
*2
The % value denotes the percentage to the inverter rated output
current. It is not the percentage to the motor rated current.
*3
When you set the electronic thermal relay function dedicated
to the Mitsubishi Electric constant-torque motor, this characteristic
curve applies to operation at 6 Hz or higher.
During Transportation
–20 °C to +65 °C
90 % RH or less
(non condensing)
10000 m
042
070
30
40
20
30
20
25
080
120
30
40
25
35
20
30
100
60
50
40
160
70
60
40

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740-012sc

Table of Contents