Mitsubishi Electric FR-D720S-008SC Original Instruction page 25

Fr-d700 sc series installation guideline fr-d720s-008sc to 100sc-ec fr-d740-012sc to 160sc-ec
Table of Contents

Advertisement

Parameter Name
Control circuit
257
capacitor life display
Main circuit capacitor
258
life display
Main circuit capacitor
259
life measuring
PWM frequency
260
automatic switchover
Power failure stop
261
selection
Terminal 4 input
267
selection
Monitor decimal digits
268
selection
269
Parameter for manufacturer setting. Do not set.
Magnitude of
295
frequency change
setting
296
Password lock level
297
Password lock/unlock
298
Frequency search gain
Rotation direction
299
detection selection at
restarting
Communication
338
operation command
source
Communication speed
339
command source
Communication
340
startup mode
selection
Communication
342
EEPROM write
selection
Communication error
343
count
450
Second applied motor
Remote output
495
selection
496
Remote output data 1
Stop mode selection at
502
communication error
503
Maintenance timer
Maintenance timer
504
alarm output set time
549
Protocol selection
PU mode operation
551
command source
selection
*1
Available only for the three-phase power input specification model.
*2
The initial value differs according to the voltage class:
200 V/400 V
Setting Range
Initial Value
(0 to 100 %)
100 %
(0 to 100 %)
100 %
0, 1 (2, 3, 8, 9)
0
0, 1
0
0, 1, 2
0
0, 1, 2
0
0, 1, 9999
9999
0, 0.01, 0.10, 1.00,
0
10.00
1 to 6, 101 to 106,
9999
9999
1000 to 9998
9999
(0 to 5, 9999)
0 to 32767, 9999
9999
0, 1, 9999
0
0, 1
0
0, 1, 2
0
0, 1, 10
0
0, 1
0
0
0, 1, 9999
9999
0, 1, 10, 11
0
0 to 4095
0
0,1, 2
0
0 (1 to 9998)
0
0 to 9998, 9999
9999
0, 1
0
2, 4, 9999
9999
Parameter Name
555
Current average time
556
Data output mask time
Current average value
557
monitor signal output
reference current
PTC thermistor
561
protection level
Energization time
563
carrying-over times
Operating time
564
carrying-over times
571
Holding time at a start
Output interruption
575
detection time
Output interruption
576
detection level
Output interruption
577
cancel level
Traverse function
592
selection
Maximum amplitude
593
amount
Amplitude
594
compensation amount
during deceleration
Amplitude
595
compensation amount
during acceleration
Amplitude
596
acceleration time
Amplitude
597
deceleration time
Acceleration time at a
611
restart
Speed smoothing
653
control
Regeneration
665
avoidance frequency
gain
Input phase loss
*1
872
protection selection
Regeneration
882
avoidance operation
selection
Regeneration
883
avoidance operation
level
Regeneration
avoidance
885
compensation
frequency limit value
Regeneration
886
avoidance voltage
gain
888
Free parameter 1
PARAMETER
Setting Range
Initial Value
0.1 to 1 s
1 s
0 to 20 s
0 s
Rated
0 to 500 A
inverter
current
0.5 to 30 k ,
9999
9999
(0 to 65535)
0
(0 to 65535)
0
0.0 to 10.0 s, 9999
9999
0 to 3600 s, 9999
1 s
0 to 400 Hz
0 Hz
900 to 1100 %
1000 %
0, 1, 2
0
0 to 25 %
10 %
0 to 50 %
10 %
0 to 50 %
10 %
0.1 to 3600 s
5 s
0.1 to 3600 s
5 s
0 to 3600 s,
9999
9999
0 to 200 %
0
0 to 200 %
100
0, 1
1
0, 1, 2
0
400 V/
300 to 800 V
*2
780 V DC
0 to 10 Hz,
6 Hz
9999
0 to 200 %
100 %
0 to 9999
9999
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740-012sc