Simple Setting Mode

<Operation>
[Simple setting mode (hysteresis mode)
In the simple setting mode, the set value, hysteresis and delay time can be changed while checking the
current pressure value (main display).
(1) Press and hold the SET button between 1 and 3 seconds in measurement mode. [SEt] is displayed on
the main display. When the button is released while in the [SEt] display, the current pressure value is
displayed on the main display, [P_1] or [n_1] is displayed on the sub display (left), and the set value is
displayed on the sub display (right) (Flashing).
(2) Change the set value with the UP or DOWN button, and press the SET button to set the value. Then,
the setting moves to hysteresis setting. (The snap shot function can be used. (Refer to page 55.))
(3) Change the set value with the UP or DOWN button, and press the SET button to set the value. Then,
the setting moves to the delay time of the switch output.
(The snap shot function can be used. (Refer to page 55.))
(4) The delay time of the switch output can be selected by pressing the UP or DOWN button at the ON and
OFF point of the switch output.
Delay time setting can prevent the output from chattering.
The delay time can be set in the range 0.00 to 60.00 sec. in 0.01 sec. increments.
(5) Press the SET button for less than 2 seconds to complete the OUT1 setting.
[P_2] or [n_2] is displayed on the sub screen (left). Continue with setting the OUT2.
Press and hold the SET
to measurement mode.
1: Selected items (1) to (4) become valid after pressing the SER button.
2: After enabling the setting by pressing the SET button, it is possible to return to measurement mode by pressing the SET
button for 2 seconds or longer.
3: When the output mode (refer to page 29) is set to error output or output OFF, the simple setting mode cannot be used.
(The setting changes to measurement mode by releasing the button when [SEt] is displayed.)
button for 2 seconds or longer to complete the setting. The product will return
-23-