Suitable actuators

Ordering

Product documentation

Technical design

Heating curve chart
Compensating
variables
Siemens
Building Technologies
Room unit QAW70
with room sensor, time
switch, setpoint ad-
justment and room
temperature readjust-
ment (setting knob)
All electric or electro-hydraulic actuators for three-position control from Siemens can
be used:
Operating voltage AC 24...230 V
Maximum running time 6 minutes (recommended: 2 to 3 minutes)
All electro-thermal actuators for two-position control:
Operating voltage AC 24...230 V
Running time 8 to 16 minutes
When ordering, please give type reference according to "Type summary"
If a controller with a weekly time switch is required, the type RVP201.0 or RVP211.0
plus the required time switch (AUZ3.7 or AUZ3.1) must be ordered
Sensors, room unit, actuator and valve must be ordered as separate items
Type of documentation
Basic Documentation
Installation Instructions (languages: de, en, fr,
nl, sv, fi, da, it, es, el)
Operating Instructions (languages: de, en, fr,
nl, sv, fi, da, it, es, el)
CE Declaration of Conformity
Environmental Declaration
T
V
4
110
100
90
80
70
60
50
40
30
20
20
10
0
Weather-compensated control: the setpoint of the flow or boiler temperature is con-
tinuously shifted in function of the outside temperature (via the outside sensor). As-
signment of the flow temperature to the actual outside temperature is made via the
heating curve. Its slope is adjustable
Heating Controller RVP201, RVP211
Document no.
P2464
G2464
B2464
T2464
E2464
3,5
3
2,75
2,5
2,25
1,75
1,5
1,25
0,75
0,5
0,25
-10
-20
-30
Room unit
QAA50.110/101,
with LCD display, room
temperature measure-
ment and display, knob
for manual setpoint
readjustments, operat-
ing- and presence
button
Part no.
74 319 0614 0
74 319 0613 0
2
1
T
Outside temperature [°C]
A
T
T
Flow temperature[°C]
A
V
CE1N2464en