Panel Mounting
For applications requiring more than one GCG001 or
when locating the module away from a backplane, panel-
mounting is also possible. The GCG001's two captive
machine screws can be used for attaching the unit to a
panel.
Note: The panel must have a minimum thickness of
2.4mm (0.094in). Leave a minimum of 75 mm
(3 in.) open above and below the module to
allow for ventilation and connector access.
Drill two mounting holes using the spacing shown
1.
in the following drawing and tap for M3.5 screws
(3.5 x 0.6 mm).
Align the module's two mounting screws with the
2.
mounting holes in the panel.
Using a Philips screwdriver, tighten the two screws
3.
to a maximum torque of 0.5 Nm (4.4 in-lbs).
Grounding
The GCG001 module provides a grounding connection on
the power plug. The panel in which the GCG001 module or
RX3i Universal Backplane is mounted to must have a
safety ground connection to protective earth. This ground wire must be at least 1.5 mm
AWG).
Connect the frame ground connection on the power plug to protective earth.
Terminate all ground wires at the same grounding point.
Make all ground wires as short as possible.