York XP036 Technical Manual page 28

R-410a zf / zr / xp series 3 - 5 ton 60 hertz
Hide thumbs Also See for XP036:
Table of Contents

Advertisement

Electric Heat Minimum Supply Air
Size
(Tons)
208/230-1-60
208/230-3-60
036
(3.0)
208/230-1-60
048
208/230-3-60
(4.0)
208/230-1-60
208/230-3-60
060
(5.0)
Indoor Blower Specifications (Belt Drive)
Size
(Tons)
HP
RPM
1-1/2
1725
036
(3.0)
1-1/2
1725
1-1/2
1725
048
(4.0)
1-1/2
1725
060
1-1/2
1725
(5.0)
2
1725
Power Exhaust Specifications
Model
Voltage
2PE04703025
208/230-1-60
2PE04703046
460-1-60
1. Motors are multi-tapped and factory wired for high speed.
Electric Heat Multipliers
Voltage
Nominal
240
480
600
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Johnson Controls Unitary Products
Voltage
5
900
900
460-3-60
-
600-3-60
-
1200
1200
460-3-60
-
600-3-60
-
1500
1500
460-3-60
-
600-3-60
-
Motor
Datum Dia.
Eff.
SF
Frame
0.8
1.15
56
0.8
1.15
56
0.8
1.15
56
0.8
1.15
56
0.8
1.15
56
0.8
1.15
56
Motor
1
HP
RPM
1/2
1725
1/2
1725
Applied
208
230
460
575
Minimum Supply Air (CFM)
Heater kW
7
10
900
900
900
900
900
900
-
900
1200
1200
1200
1200
1200
1200
-
1200
1500
1500
1500
1500
1500
1500
-
1500
Motor Sheave
Bore (in.)
Model
(in.)
2.8 - 3.8
7/8
1VL44
4.0 - 5.0
7/8
1VP56
2.8 - 3.8
7/8
1VL44
4.0 - 5.0
7/8
1VP56
2.8 - 3.8
7/8
1VL44
4.0 - 5.0
7/8
1VP56
Motor
QTY
LRA
FLA
1
23.7
4.4
1
4.1
1.7
kW Capacity Multipliers
0.75
0.92
0.92
0.92
15
20
30
900
900
-
900
900
-
900
900
-
900
900
-
1200
1200
-
1200
1200
-
1200
1200
-
1200
1200
-
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
Blower Sheave
Datum Dia.
Bore (in.)
Model
(in.)
6.0
1
AK64
6.2
1
AK66
5.2
1
AK56
5.7
1
AK61
5.2
1
AK56
5.2
1
AK56
Fuse Size
MCA
5.5
8
2.1
5
1
251933-YTG-J-1009
Belt
A37
A39
A36
A38
A36
A38
CFM @
0.1 ESP
1350
1350
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp060Xp048

Table of Contents