York XP036 Technical Manual page 33

R-410a zf / zr / xp series 3 - 5 ton 60 hertz
Hide thumbs Also See for XP036:
Table of Contents

Advertisement

XP036-060 (Belt Drive High Static) (Continued)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-3-60 15.6 110.0 24.4
230-3-60 15.6 110.0 24.4
060
(5.0)
460-3-60 7.7
52.0
575-3-60 5.8
38.9
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
2.3
8.2
0.0
2.3
8.2
0.0
12.1
1.3
4.1
0.0
9.1
1.3
3.6
0.0
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
E05
4.0
1
11.1
E07
5.6
1
15.5
E10
8.0
1
22.2
E15
11.9
2
33.0
E20
15.9
2
44.1
E30
22.2
2
61.6
None
-
-
E05
5.3
1
13.3
E07
7.5
1
18.8
E10
10.6
1
26.6
E15
15.9
2
39.9
E20
21.2
2
53.2
E30
29.6
2
74.3
None
-
-
E07
6.8
1
8.5
E10
10.1
1
12.7
E15
13.6
2
17.1
E20
19.5
2
24.5
E30
28.8
2
36.1
None
-
-
E10
10.6
1
10.6
E15
15.9
1
16.0
E20
21.2
2
21.3
E30
30.4
2
30.5
Max
2
Fuse
/
1
MCA
3
Breaker
(Amps)
Size
(Amps)
-
30.0
40
43.9
50
49.4
60
57.8
60
71.3
80
85.2
90
107.0
110
-
30.0
40
45.9
50
52.6
60
61.9
70
77.8
80
93.7
100
119.0
125
-
15.0
20
25.2
30
30.2
35
35.5
40
44.3
45
58.3
60
-
11.9
15
24.6
25
31.0
35
37.4
40
48.5
50
251933-YTG-J-1009
73

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp060Xp048

Table of Contents