York XP036 Technical Manual page 37

R-410a zf / zr / xp series 3 - 5 ton 60 hertz
Hide thumbs Also See for XP036:
Table of Contents

Advertisement

XP036-060 (Belt Drive) (Continued)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-1-60 26.2 134.0 41.0
230-1-60 26.2 134.0 41.0
208-3-60 15.6 110.0 24.4
060
(5.0)
230-3-60 15.6 110.0 24.4
460-3-60 7.7
52.0
575-3-60 5.8
38.9
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
2.3
7.6
10.0
2.3
7.6
10.0
2.3
5.2
10.0
2.3
5.2
10.0
12.1
1.3
2.6
5.0
9.1
1.3
2.0
4.0
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
-
E05
4.0
1
19.2
E07
5.6
1
26.9
E10
8.0
1
38.5
E15
11.9
2
57.2
E20
15.9
2
76.4
E30
22.2
2
106.7
None
-
-
-
E05
5.3
1
23.0
E07
7.5
1
32.6
E10
10.6
1
46.1
E15
15.9
2
69.1
E20
21.2
2
92.2
E30
29.6
2
128.7
None
-
-
-
E05
4.0
1
11.1
E07
5.6
1
15.5
E10
8.0
1
22.2
E15
11.9
2
33.0
E20
15.9
2
44.1
E30
22.2
2
61.6
None
-
-
-
E05
5.3
1
13.3
E07
7.5
1
18.8
E10
10.6
1
26.6
E15
15.9
2
39.9
E20
21.2
2
53.2
E30
29.6
2
74.3
None
-
-
-
E07
6.8
1
8.5
E10
10.1
1
12.7
E15
13.6
2
17.1
E20
19.5
2
24.5
E30
28.8
2
36.1
None
-
-
-
E10
10.6
1
10.6
E15
15.9
1
16.0
E20
21.2
2
21.3
E30
30.4
2
30.5
251933-YTG-J-1009
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
52.7
70
76.7
90
86.3
100
100.7
110
124.2
125
148.2
150
186.1
200
52.7
70
80.3
100
91.7
110
107.9
110
135.5
150
163.1
175
206.8
225
37.0
45
50.9
60
56.4
60
64.8
70
78.3
80
92.2
100
114.0
125
37.0
45
52.9
60
59.6
70
68.9
70
84.8
90
100.7
110
126.0
150
18.5
25
28.7
30
33.7
35
39.0
40
47.8
50
61.8
70
14.3
20
27.0
30
33.4
35
39.8
40
50.9
60
89