York XP036 Technical Manual page 34

R-410a zf / zr / xp series 3 - 5 ton 60 hertz
Hide thumbs Also See for XP036:
Table of Contents

Advertisement

251933-YTG-J-1009
XP036-060 (Direct Drive)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-1-60 16.6
88.0
230-1-60 16.6
88.0
036
(3.0)
208-3-60 12.8
95.0
230-3-60 12.8
95.0
208-1-60 21.1 113.0 33.0
230-1-60 21.1 113.0 33.0
048
(4.0)
208-3-60 16.0 120.0 25.0
230-3-60 16.0 120.0 25.0
74
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
26.0
1.6
6.0
0.0
26.0
1.6
6.0
0.0
20.0
1.6
6.0
0.0
20.0
1.6
6.0
0.0
2.3
7.6
0.0
2.3
7.6
0.0
2.3
7.6
0.0
2.3
7.6
0.0
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
E05
4.0
1
19.2
E07
5.6
1
26.9
E10
8.0
1
38.5
E15
11.9
2
57.2
E20
15.9
2
76.4
None
-
-
E05
5.3
1
23.0
E07
7.5
1
32.6
E10
10.6
1
46.1
E15
15.9
2
69.1
E20
21.2
2
92.2
None
-
-
E05
4.0
1
11.1
E07
5.6
1
15.5
E10
8.0
1
22.2
E15
11.9
2
33.0
E20
15.9
2
44.1
None
-
-
E05
5.3
1
13.3
E07
7.5
1
18.8
E10
10.6
1
26.6
E15
15.9
2
39.9
E20
21.2
2
53.2
None
-
-
E05
4.0
1
19.2
E07
5.6
1
26.9
E10
8.0
1
38.5
E15
11.9
2
57.2
E20
15.9
2
76.4
None
-
-
E05
5.3
1
23.0
E07
7.5
1
32.6
E10
10.6
1
46.1
E15
15.9
2
69.1
E20
21.2
2
92.2
None
-
-
E05
4.0
1
11.1
E07
5.6
1
15.5
E10
8.0
1
22.2
E15
11.9
2
33.0
E20
15.9
2
44.1
None
-
-
E05
5.3
1
13.3
E07
7.5
1
18.8
E10
10.6
1
26.6
E15
15.9
2
39.9
E20
21.2
2
53.2
Max
2
Fuse
/
1
MCA
3
Breaker
(Amps)
Size
(Amps)
-
28.4
35
52.4
60
62.0
70
76.4
80
99.9
100
123.9
125
-
28.4
35
56.0
60
67.4
70
83.6
90
111.2
125
138.8
150
-
23.6
30
37.5
45
43.0
50
51.4
60
64.9
70
78.8
80
-
23.6
30
39.5
45
46.2
50
55.5
60
71.4
80
87.3
90
-
36.3
45
60.3
70
69.9
80
84.4
90
107.8
110
131.8
150
-
36.3
45
63.9
70
75.3
80
91.5
100
119.1
125
146.7
150
-
29.9
40
43.8
50
49.3
60
57.7
60
71.2
80
85.1
90
-
29.9
40
45.8
50
52.5
60
61.8
70
77.7
80
93.6
100
Johnson Controls Unitary Products

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp060Xp048